Prediction of Cable Thermal Failure in Switchgear Rooms of Nuclear Power Plants Based on Numerical Simulation and Deep Learning
Xu Zhai, Jiling Wu, Hongru Zhao, Jun Zhao, Xinhui Fu, Jinlong Zhao
Key points
From the paper's conclusion- These findings demonstrate that deep learning models can efficiently and accurately predict temperature evolution under FDS-simulated fire scenarios in a nuclear power plant switchgear room, thereby providing methodological support for fire protection design and emergency decision making.
Abstract
Thermal failure of critical cables in nuclear power plants may result in the loss of safety functions, thereby compromising the safe and stable operation of the plant. This study focuses on the switchgear room of a nuclear power plant and investigates cable thermal failure under FDS-simulated fire scenarios with varying HRR, while the ignition location, ventilation, compartment openings, and cable arrangement are fixed, employing numerical simulation and deep learning approaches. First, numerical simulations of switchgear cabinet fires were conducted using the Fire Dynamics Simulator (FDS) for 15 different heat release rates (HRR). Second, to address the limitation that existing models mainly predict static outcomes, three deep learning models were trained to capture the continuous dynamic temperature evolution on datasets derived from the simulation results, and their predictive performance was evaluated using the R2, RMSE, and MAE. Third, taking 330 °C as the thermal failure threshold for cables, the thermal failure behavior under representative HRR conditions was predicted. The results indicate that the MLP model achieves the best prediction accuracy, with R2, RMSE, and MAE values of 0.96, 11.63, and 5.77, respectively, whereas the Transformer model exhibits the poorest performance, with corresponding values of 0.90, 28.23, and 9.92. Using the optimal MLP model, the thermal failure behavior of cables under typical conditions was further analyzed. The predictions reveal that the critical HRR of the switchgear cabinet at which the critical cables reach thermal failure is 550 kW, and the time to failure exhibits a nonlinear decay with increasing HRR. Specifically, at HRR levels of 702 kW and 1002 kW, the predicted failure times are 709 s and 594 s, respectively. These findings demonstrate that deep learning models can efficiently and accurately predict temperature evolution under FDS-simulated fire scenarios in a nuclear power plant switchgear room, thereby providing methodological support for fire protection design and emergency decision making.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Study on temperature prediction and early warning of building resistive electrical circuit fire: A mathematics modelResults in Engineering · 2025
- A transformer guided multi modal learning framework for predictive and causal assessment of thermal runaway in high energy batteriesScientific Reports · 2025
- GridForge: An Open Physics-Informed Digital Twin and Benchmark Suite for UK 11 kV Underground Distribution CablesarXiv · 2026
- Multi-Sensor Spatiotemporal Feature Fusion for Early Warning of Cable Fires in Power Cable Tunnels.Sensors (Basel, Switzerland) · 2026
- Thermally Adaptive Multi-Scale Feature Fusion and Attention-Driven Channel Recalibration for Lightweight Infrared Electrical Substation InspectionDiscover Artificial Intelligence · 2026
- Simulation-Based Ampacity Assessment of Cable Joints Based on Hotspot-Temperature InversionElectronics · 2026