Flow Coefficient as a Normalising Operating Parameter for Comparison of Drop-in Fluid Replacement in Centrifugal Compressors

Jordan Dickenson, James R. Bull, Jovana Radulovic, James M. Buick

Key points

From the paper's conclusion
  • Assessing the fluid replacement in a fixed geometry is complicated by the choice of operating parameter: at a matched mass flow rate, fluids with different densities will exhibit different volumetric flow.

Abstract

The phase-out of high-GWP refrigerants means working fluids are increasingly replaced in compressors already designed and sized for the original fluid. Assessing the fluid replacement in a fixed geometry is complicated by the choice of operating parameter: at a matched mass flow rate, fluids with different densities will exhibit different volumetric flow. This study uses the flow coefficient as the main flow-side operating parameter, with the mass flow rate being calculated individually for each fluid and rotational speed so that all fluids are compared at the matched non-dimensional operating point. Eight working fluids—air, nitrogen, argon, carbon dioxide, R22, R134a, R1234yf and R1234ze(E)—were simulated in a single fixed-geometry centrifugal impeller geometry using ANSYS2024 R2 CFX across six rotational speeds from 10,000 to 20,000 RPM and six flow coefficients. The efficiency optima of all eight fluids cluster to a common flow coefficient between 0.0636 and 0.0697. However, the width of the characteristic and the onset of choke remain fluid-dependent. While the low-density fluids operate over the full range of flow coefficients, the refrigerants exhibit choke at the higher end of the flow coefficient range, a feature which increases with the rotational velocity.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Flow Coefficient as a Normalising Operating Parameter for Comparison of Drop-in Fluid Replacement in Centrifugal Compressors — Science Skim