Spectral Attribution and Measurement Adequacy in a Belt-Driven Motor-Generator Set

Florențiu Deliu, Ciprian Popa, Petrică Popov, Iancu Ciocioi, Adelina Bordianu, Tiberiu Pazara, Georgiana Andrei, Gheorghe Samoilescu

Key points

From the paper's conclusion
  • Second, attribution to the generator shaft-order and nominal 50 Hz harmonic families accounts for 73.6–93.2% of the spectral energy in the five vibration spectra retained for mechanical interpretation and 83.4–85.0% of the acoustic spectral energy.

Abstract

Vibro-acoustic diagnostics of small generating sets are usually reported as a severity figure and a list of identified fault frequencies. This paper reports what happens when the same campaign is also asked what it could not have identified. Three measurement runs on a belt-driven set—a 7.5 kW induction motor driving a 6 kW synchronous generator on a frame that is not fastened to the floor—produced six velocity spectra and three A-weighted noise spectra, from which we build a low-order source–path model in Simulink, calibrate it on a disjoint subset, and use it to inject five named fault mechanisms. Three results follow, two of them about the measurement rather than the machine. First, five velocity spectra exhibit dominant common-mode contamination within 10–25 Hz, supported by approximately 0.2% interchannel agreement in equivalent sensor-output voltage. Empirical disturbance subtraction reduces the affected 10–1000 Hz RMS velocity estimates by 10–25%, corresponding to apparent excesses of 11–33% relative to the corrected values. These estimates remain conditional on the adopted disturbance model. Second, attribution to the generator shaft-order and nominal 50 Hz harmonic families accounts for 73.6–93.2% of the spectral energy in the five vibration spectra retained for mechanical interpretation and 83.4–85.0% of the acoustic spectral energy. Nevertheless, 233 of 597 detected acoustic components (39.0%) remain unattributed. A secondary 9.28 Hz sideband pattern in the transverse run 101 CH4 spectrum comprises 23 frequency-matched components, including 22 exclusive assignments outside the two principal harmonic families, and is excluded from the principal attribution results. The generator shaft-order comb extends to at least order 31, while the available spectral resolution prevents independent extraction of selected conventional fault indicators under the adopted three-line Hanning procedure. Third, four-fold leave-one-spectrum-out recalibration yields a geometric-mean normalized spectral-shape error factor of 2.30, numerically close to the original calibration factor of 1.97, whereas the original fixed-calibration held-out comparison yields 3.77 for run 102 CH4. Absolute-level and cross-machine predictive performance remain unverified, while the exceptional run 103 CH4 response cannot support fault-specific attribution.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Spectral Attribution and Measurement Adequacy in a Belt-Driven Motor-Generator Set — Science Skim