Materials (Basel, Switzerland)

Response-Specific Thermal Equivalence of Full-Scale Multi-Material Fire-Door Systems Under Seven Fire Histories.

Bartłomiej Sędłak, Paweł Sulik, Daniel Izydorczyk

Fire Research Department, Building Research Institute (ITB), 21 Ksawerów St., 02-656 Warsaw, Poland.

Key points

From the paper's conclusion
  • Thus, AUC is a useful candidate descriptor for the tested leaf responses, but not a universal measure of system-wide thermal equivalence.

Abstract

Fire-resistance classification relies on reproducible standard heating, whereas real and design fires can impose different thermal histories. We assessed whether matching instantaneous furnace temperature or cumulative furnace-temperature area under the curve (AUC) provides comparable unexposed-side responses in fire-door systems. Seven furnace histories were examined using wooden, glazed aluminium and steel doors tested simultaneously. Frame-rebate, 25 mm, 100 mm and general leaf-surface temperature rises were compared at matched pre-E states. Each history was represented by one furnace run, so comparisons are descriptive rather than inferential. At 700 °C, frame-rebate temperature-rise spreads across histories reached approximately 82-156 K. Across seven standard-fire-referenced states (500-800 °C), AUC matching yielded lower mean absolute error in 58/63 group-mean leaf-zone comparisons and 52/63 local-maximum comparisons. Using four common histories, leaf-zone absolute spreads were smaller than rebate spreads in 54/54 matched-AUC comparisons. Magnitude-normalised rankings depended on the chosen denominator, and the results do not establish an engineering equivalence threshold. Burner energy did not yield transferable severity or integrity thresholds. Thus, AUC is a useful candidate descriptor for the tested leaf responses, but not a universal measure of system-wide thermal equivalence.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Response-Specific Thermal Equivalence of Full-Scale Multi-Material Fire-Door Systems Under Seven Fire Histories — Science Skim