Fluids

Cooling Performance Prediction Model of Indirect Dry Cooling System in Power Plants

Hui Wang, Jianhui Zeng, Xinning Song, Zhanyang Li, Xiaopeng Wu, Lei Chen

Key points

From the paper's conclusion
  • These models predict system performance rapidly and with engineering accuracy over the full operating range and offer a practical, low-cost tool for operational optimization, performance prediction and circulating-water allocation of indirect dry cooling systems in power plants.

Abstract

Indirect dry cooling systems are key cooling equipment in water-scarce power plants, and their cooling performance is strongly affected by ambient temperature and crosswind. Reliable performance prediction under variable meteorological conditions is therefore essential for safe, economic and efficient unit operation, but conventional prediction relies either on time-consuming computational fluid dynamics or on black-box algorithms that lack physical transparency. This study aims to provide a physically explicit and computationally inexpensive prediction approach for an indirect dry cooling system. A half-tower numerical model of the indirect dry cooling system serving a 2 × 660 MW power plant is established, and a multi-scale heat-conservation model that couples the steam condenser, the air-cooled heat exchanger and the individual cooling sectors is developed and validated against design conditions. The results show that crosswind produces pronounced sector-level asymmetry: windward sectors gain cooling capacity, whereas lateral crosswind sectors suffer severe airflow loss and hot-air recirculation, while rising ambient temperature uniformly weakens the cooling capacity of all sectors. On this basis, explicit polynomial prediction models expressed as functions of ambient temperature and wind speed are established for total heat transfer rate, ventilation rate, sector airflow, inlet air temperature and sector heat transfer. These models predict system performance rapidly and with engineering accuracy over the full operating range and offer a practical, low-cost tool for operational optimization, performance prediction and circulating-water allocation of indirect dry cooling systems in power plants.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Cooling Performance Prediction Model of Indirect Dry Cooling System in Power Plants — Science Skim