Engineering Research Express

A Hybrid Physics-Data Decision-Support Framework for Real-Time Prediction and Season-Adaptive Optimization of a Natural Evaporative Water Cooler

Milan Trivedi, Diptesh Patel

Key points

From the paper's conclusion
  • This study presents a hybrid physics–data decision-support framework for a natural evaporative water cooler that unifies real-time temperature-drop prediction with season-adaptive operational optimization and delivers both as a deployable tool.

Abstract

This study presents a hybrid physics–data decision-support framework for a natural evaporative water cooler that unifies real-time temperature-drop prediction with season-adaptive operational optimization and delivers both as a deployable tool. A one-dimensional resistance-network heat-transfer model of the cooler forms the physics layer, and machine-learning surrogates trained on 81 balanced experimental runs spanning summer, monsoon and winter (dry-bulb temperature 19.3–42 °C, relative humidity 24.6–80.5 %, temperature drop 1.8–9.8 °C) form the data layer. Under ten-fold cross-validation a Gaussian-process regressor is the most accurate model (R2 = 0.973), while a tuned artificial neural network (R2 = 0.941) is selected as the deployed surrogate because it compiles to a compact, dependency-free model of 241 parameters suited to low-cost field hardware. The neural network is coupled with a differential-evolution search that, for any ambient dry-bulb temperature and relative humidity, returns the operational settings (fan speed, sprinkled-water flow rate and coil-water velocity) that maximize the temperature drop at a fixed, design-selected viscose-fibre pad, generalizing three discrete seasonal optima to a continuous envelope. The global optimality of the search was verified against an exhaustive grid in 1500 independent runs, and the best of five runs came within 0.01 °C of the global optimum in 97 % of cases. On twelve independent experimental runs the framework predicts the temperature drop with R2 = 0.985 and a mean absolute percentage error of 3.6 %. The framework is delivered as a self-contained, browser-based console that returns recommended settings and predicted performance from the ambient conditions and the inlet water temperature, offering an accessible route to energy-efficient, refrigerant-free water cooling for hot regions.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers