Design of an Integrated Large-Angle Open-Ring Device for In Situ X-Ray Imaging Inspection of Ultra/Extra High-Voltage Gas-Insulated Metal-Enclosed Transmission Lines
Miaoling Li, Weihua Shi, Chao Li, Chaohua Wang, Ming Luo, Zhiyong Chen, Dalei Zu, Jie Lian
Key points
From the paper's conclusion- Therefore, an integrated large-angle open-ring mechanical device, mainly consisting of a fixed open annular bracket and an open rotating ring, is proposed and developed for X-ray inspection of GILs.
Abstract
Ultra/extra high-voltage gas-insulated metal-enclosed transmission lines (GILs) feature a large shell diameter, compact installation, and limited testing space, which restricts the application of in-situ X-ray imaging detection technology. Therefore, an integrated large-angle open-ring mechanical device, mainly consisting of a fixed open annular bracket and an open rotating ring, is proposed and developed for X-ray inspection of GILs. The assembled complete mechanism maintains a consistent opening angle and position and can be directly pushed into place and wrapped around the GIL unit during detection tasks. Multiple pairs of rollers are employed to form a size-adjustable annular guide rail on the fixed open bracket. The open rotating ring is mounted inside the guide rail to form a bidirectional clamping and rolling constraint structure. Installation bases for imaging detectors are designed on both sides of one end of the open rotating ring, whereas only one base for the radiation source is arranged on the other end. This configuration enables two imaging modes: vertical X-ray transmission and oblique X-ray transmission through the GIL unit. The rotating ring is synchronously driven by a servo motor via a pair of gears and a timing belt, enabling a circumferential swing angle of 220–230°. This device is suitable for X-ray imaging inspection of multi-specification ultra/extra-high voltage GIL. It can effectively avoid imaging obstructions such as flanges and brackets during data acquisition. It possesses good engineering application potential for factory sampling, in-service maintenance and other non-destructive testing scenarios of GIL.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Transmission Characteristics and Structural Optimization of Lightguide Rods for Optical Partial Discharge Detection.Sensors (Basel, Switzerland) · 2026
- Spatially controlled x-ray field generation by a twin cylindrical x-ray gun.The Review of scientific instruments · 2026
- Bypass Sheath Voltage Limiters at Cable-to-GIS Terminations: Geometry-Resolved Connection-Lead Impedance for Insulation Coordination Under Very Fast Transient OvervoltagesEnergies · 2026
- Magnetic field sensitivity study of an X-ray GEM diagnostic for RFX-mod2Journal of Instrumentation · 2026
- Modeling and Analysis of Slope-Dependent Response Properties of Gas-Insulated Transmission Line System Under Vehicle-Induced LoadsEng · 2026
- Flexible Wireless Passive Resonance Ring Sensor for Nondestructive Crack Monitoring of Metal Structures.Micromachines · 2026