Effectiveness of Automatic Disconnection of Supply in the Islandable TN–C Household Electrical Installation Equipped with Photovoltaic Source and Battery Energy Storage System
Roman Korab, Mirosław Kiełboń, Paweł Kubek, Andrzej Latko, Krzysztof Maźniewski, Bernard Witek, Dominik Duda, Agnieszka Dziendziel,
Key points
From the paper's conclusion- Therefore, to verify the effectiveness of the ADS, measurements of short-circuit currents and touch voltage waveforms were taken during actual short circuits.
Abstract
Photovoltaic sources and energy storage are increasingly being installed in power supply systems of residential buildings. As a result, consumer installations are being transformed into prosumer installations, typically operating as grid-connected, but often also with the option of island operation. Legally binding standards specify the technical requirements that an islandable prosumer electrical installation (PEI) must meet, including those regarding shock protection. Unfortunately, when older installations, constructed in accordance with the then-current standards, are converted into PEI systems, these requirements are not always met. This raises the question of the safety of users operating islandable PEIs that do not meet up-to-date requirements. The aim of this paper is to assess the effectiveness of shock protection in the case of indirect contact (automatic disconnection of supply—ADS) in various operating modes of the reference islandable PEI constructed in the TN–C earthing system, i.e., incompatible with current standards. First, the effectiveness of ADS was assessed using commonly applied calculation and measurement methods. Contrary conclusions were obtained for island operation modes of the reference PEI. Therefore, to verify the effectiveness of the ADS, measurements of short-circuit currents and touch voltage waveforms were taken during actual short circuits. The obtained results confirm that the requirements for protection against electric shock in case of indirect contact (ADS) were met in all operating modes of the analyzed PEI.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Characteristics of the Use of a Photovoltaic Micro-Installation for a Residential Unit in a Multi-Family Building: A Case Study from North-Eastern PolandEnergies · 2026
- Planning-Stage Assessment of Battery-Supported Regional Islanding: A South Australian Case StudyarXiv · 2026
- An Overview of Anti-Islanding Protection Schemes in PV-Based MicrogridsEnergies · 2026
- Analysis of the Impact of Distributed Generation on the Frequency Stability and Rotational Inertia of the Electric SystemElectronics · 2026
- Dynamic Assessment of Voltage Regulation Capacity in High-Penetration PV and Electrochemical Energy Storage Distribution Networks Considering Response Delay and Source–Load CorrelationComputation · 2026
- Energy Storage as a Tool to Increase the Security and Energy Efficiency of Household Electricity in North-Western Poland in the Sustainable Management of Micro-Installation PotentialSustainability · 2026