Real-Time Frequency Regulation of a Two-Area Power Plant with PV Grid and Thermal Generator Using an Adaptive Nonlinear Controller
Emre Çelik, Nihat Öztürk, Gulshan Sharma, Davut İzci, Cemil Ocak, Mahmoud Abdel-Salam
Key points
From the paper's conclusion- In the work, an adaptive nonlinear PI (ANPI) controller is designed and its FR performance is evaluated on a two-area power plant consisting of photovoltaic (PV) system and thermal generator.
Abstract
When the electricity generation does not meet the consumption, it causes undulations in area frequency and exchanging power in transmission lines. Frequency regulation (FR) is an inevitable mechanism for damping such undulations over the grid. In the work, an adaptive nonlinear PI (ANPI) controller is designed and its FR performance is evaluated on a two-area power plant consisting of photovoltaic (PV) system and thermal generator. In the controller presented, a sector-bounded nonlinear gain K based on a hyperbolic function is incorporated in cascade with a classical PI controller. To increase the degree of freedom during the design stage, the hyperbolic function is shaped by the two parameters. Stochastic fractal search (SFS) algorithm via the minimization of ITAE criterion is adopted to identify the best combination of controller parameters in attempting to acquire the maximum possible benefit from the controller. The ANPI controller is contrasted against similar works in the arena. It is found that using the ANPI controller the ITAE criterion is lowered to 2.291 from its known best value of 2.343, yielding an improvement of 2.25%. In line with this reduction, larger improvements up to 44.6% in settling time and frequency/tie-line deviations are obtained by employing the proposed approach. As a result, undulations in frequency and tie-line power responses are suppressed, and the responses are able to achieve the steady state value of zero more shortly. After carrying out the analysis of robustness to parameter uncertainty, measurement noise and renewable generation intermittence, the ANPI controller appears to perform robustly. The proposed method is affirmed through using the OPAL-RT OP4605XG2 real-time simulator.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Robust load frequency control in renewable integrated Multi Area grids using hybrid SA and QIO tuned PIDF controllerScientific Reports · 2025
- Load Frequency Regulation for Thermal Units Integrated with Renewable Energy Sources and Energy Storage SystemsEnergies · 2026
- Load Frequency Control of Multi-Area Power System Using Hybrid Fuzzy Tilt Integral with Tilt Integral Derivative-Based Fractional Order ControllerAlgorithms · 2026
- Optimal load frequency control and automatic voltage regulation in four-area interconnected power systems using FOPD-FOPIDD2 controller design with energy valley optimizerScientific Reports · 2026
- An Intelligent Hybrid PIDF Enhanced by a Fuzzy Fractional-Order Controller for Robust Load Frequency Regulation in a Two-Area Interconnected Power SystemEnergies · 2026
- Energy Valley Optimization-Based Adaptive Fuzzy Logic Control for Grid-Connected Photovoltaic Systems: Simulation and Experimental ValidationMachines · 2026