Can Ground-Coupled Ventilation Close the Gap to Zero Carbon? Hourly Simulation and Techno-Economic Assessment of a Solar Decathlon House in Riyadh

Osamah Alanazi, Mohammad G. Kotbi, Mohammad O. Alfadil, Ahmad G. Kotbi

Computational

Key points

From the paper's conclusion
  • The pipe cooled the outdoor air by 4.8 K on average, yet saved only 2.8% of HVAC electricity (2.4% net of fan energy; 3.2% ahead of the house’s energy recovery exchanger), because ventilation is a small part of this envelope’s load; the saving reaches 32% only at 6.4 outdoor air changes per hour.

Abstract

Cooling keeps even well-designed Saudi solar houses dependent on the grid. This study asks whether open-loop ground-coupled ventilation (GCV) can move a net-zero-energy Solar Decathlon house in Riyadh towards carbon-free operation. The house was re-modeled in Revit, Carrier HAP and HelioScope and validated against the original design. A buried vitrified clay pipe (19.8 m, 0.30 m diameter, 6 m deep) was sized with a regression-based design tool and coupled hour by hour to the outdoor air required by ASHRAE 62.2 (20 L s−1), with bypass control, calculated fan power and an hourly battery model. The pipe cooled the outdoor air by 4.8 K on average, yet saved only 2.8% of HVAC electricity (2.4% net of fan energy; 3.2% ahead of the house’s energy recovery exchanger), because ventilation is a small part of this envelope’s load; the saving reaches 32% only at 6.4 outdoor air changes per hour. Grid import (4961 kWh y−1, mostly at night) fell by 2.2% with GCV, by 23% with evening loads shifted to midday, and to 50–64 kWh y−1 with a 40 kWh battery and load shifting. The GCV has a negative net present value at current tariffs. Storage and demand scheduling, not cooling load, are the binding constraints.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers