Risk-Aware Energy–Compute Scheduling for Integrated Energy Systems with Multiple Data Centers Under Extreme Weather

Haoming Li, Kunyang Li, Zhonglin Zhang, Dengfeng Chen

Key points

From the paper's conclusion
  • Extreme weather stresses the power, thermal and computing infrastructure of data centers, yet energy and computing resources are still scheduled separately.

Abstract

Extreme weather stresses the power, thermal and computing infrastructure of data centers, yet energy and computing resources are still scheduled separately. This paper presents a risk-aware energy–compute co-scheduling framework for multi-microgrid integrated energy systems hosting heterogeneous data centers. Learning and optimization exchange a single quantity: a risk-conditional exchange-capability credit. The empirical conditional value-at-risk (CVaR) tail of the net-load distribution, widened by a dispersion- and hazard-calibrated buffer, sets the import headroom of a single-step rolling mixed-integer linear program (MILP) that executes one of five operating postures chosen by offline-trained implicit Q-learning agents, subject to device, storage, queue, migration and unserved-energy constraints. Scenario-level tests over eight held-out scenarios per weather type and three replications produce positive energy-not-served (ENS) margins against rule-based and constant-posture baselines in all six comparisons, and a ten-scenario library confirms a 10/10 sign agreement. In a recorded-event replay, the ENS ratio falls from 9.751% to 2.292%. Sensitivity and scalability tests further confirm that the framework remains effective under parameter variation and at larger system sizes.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers