Analysis of the Influence of Minimum Temperature Difference in a Heat Exchanger Under Fouling on the PID Temperature Controller Settings
Mariusz Markowski, Marian Trafczynski, Slawomir Alabrudzinski, Marcin Kruzel, Krzysztof Dutkowski, Tadeusz Bohdal, Kacper Elwertowski
Key points
From the paper's conclusion- Fouling is one of the most troublesome constraints in heat exchanger operation; it reduces heat duty and, as deposits grow, changes the exchanger dynamics, causing PID temperature controllers tuned for clean conditions to lose performance.
Abstract
Fouling is one of the most troublesome constraints in heat exchanger operation; it reduces heat duty and, as deposits grow, changes the exchanger dynamics, causing PID temperature controllers tuned for clean conditions to lose performance. This study examines whether the minimum temperature difference (ΔTmin) chosen at the design stage can limit this effect. A dynamic model of a shell-and-tube crude oil preheater (220 t/h) was implemented in MATLAB/Simulink R2025b, and closed-loop responses, control-quality indices and stability margins were compared for ΔTmin = 50 K and 10 K for clean and fouled (Rf = 0.00138 m2K/W) exchangers with Ziegler–Nichols PID settings. At ΔTmin = 50 K, fouling increased the set-point ISE by 75%, the settling time from 92 s to 231 s, and the overshoot from 57% to 65%, while reducing the phase margin from 25.7° to 15.8°; retuning was necessary and restored the phase margin to 27.8°. At ΔTmin = 10 K, the corresponding changes were much smaller (ISE increased by 27%, settling time increased from 107 s to 159 s, overshoot increased from 40% to 44%, and phase margin decreased by only 3.4°), so the original settings could be retained. Disturbance-rejection ISE grew 2.2-fold at 50 K versus 1.6-fold at 10 K. A lower ΔTmin is therefore a practical design guideline for reducing fouling-induced controller retuning.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Comparison of Feedback and Feedforward Control Systems for a Counter-Current Heat ExchangerProcesses · 2026
- Temperature control model analysis of intelligent drilling fluid surface cooling equipment for high-temperature deep well working conditionsJournal of Physics: Conference Series · 2026
- Gudermannian-based error-shaped PID controller tuned via THRO for nonlinear CSTR temperature controlChaos Solitons & Fractals · 2026
- Role of temperature-dependent fluid property variations on energy pile performanceApplied Thermal Engineering · 2026
- Simplex and Random Learning-Enhanced Superb Fairy-Wren Optimization for Two-Degree-of-Freedom Temperature ControlBiomimetics · 2026
- Dual-Mode Extremum Seeking for Diffusion Systems with Boundary-Cost FeedbackarXiv · 2026