Research on Two-Stage Coordinated Optimal Control of PV-ESS Voltage in Active PV Distribution Network Based on Inverter Residual Capacity
Xinyan Li, Haifeng Zhan, Yueming Ding, Qinyue Tan
Key points
From the paper's conclusion- Therefore, this paper proposes a two-stage photovoltaic active distribution network photovoltaic storage voltage collaborative control optimization method based on the remaining capacity of the inverter.
Abstract
Under high-penetration photovoltaic integration, node voltage over-limits are frequently experienced by active distribution networks during light-load periods at noon due to reverse active power flow, while voltage sag risks are faced during nighttime or sudden drops in photovoltaic output. As a result, voltage fluctuations exhibit bidirectional violation characteristics. Existing countermeasures tend to be polarized: fast control relying on local measurements, though timely in response, is prone to voltage deviation accumulation and regional circulating currents due to the lack of global coordination; global optimization based on iterative communication, though economically superior, is hampered by a convergence speed that can hardly match the second-level fluctuations of photovoltaic output. Moreover, by neither approach can the active and reactive remaining capacities of inverters be dynamically called upon according to their real-time operating states, and thus the conflicts among voltage regulation speed, accuracy, and economy are made difficult to resolve. Therefore, this paper proposes a two-stage photovoltaic active distribution network photovoltaic storage voltage collaborative control optimization method based on the remaining capacity of the inverter. By analyzing the coupling effects of photovoltaic-storage active power output on node voltages and network losses, the dominant role of active power regulation in distribution-network loss reduction is revealed. Dynamic safety factors and harmonic correction factors are introduced to quantify the effective remaining capacity of inverters in real time, so that the regulation boundaries are adaptively updated with operating states. Based on local measurements, dynamic droop control is implemented to achieve millisecond-level autonomous suppression of voltage violations. Furthermore, a regional coordinated optimization model is constructed with the objectives of minimizing network losses and voltage deviations. Local commands are corrected through limited information exchange among adjacent regions, and thus voltage deviation accumulation and regional circulating currents are eliminated at very light communication cost. The test results show that this method can determine the actual active power command correction and reactive power command correction at different over-limit depths. After control, the reactive power output of the photovoltaic inverter fluctuates less and reduces network loss by over 40%. The global voltage throughout the day is stabilized within a narrow range of 0.95–1.01 p.u., verifying the comprehensive advantages of this method in terms of fast and slow time scale coordination and dynamic capacity utilization.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Voltage Control and Governance Strategies for Distributed Photovoltaic Integration into Distribution Networks Based on Intelligent Dynamic Voltage-Coordinated GridApplied Sciences · 2026
- Dynamic Assessment of Voltage Regulation Capacity in High-Penetration PV and Electrochemical Energy Storage Distribution Networks Considering Response Delay and Source–Load CorrelationComputation · 2026
- Design and coordinated capacity control of ESSs for typical new power system scenariosJournal of Physics: Conference Series · 2026
- Capacity and Operation Planning of Distributed Photovoltaic and Energy Storage with Screening-Based Site Assessment and Coordinated Reactive Power Compensation in Distribution NetworksEnergies · 2026
- ADBO-Optimized Smart Inverter Integration of PV/BESS for Incremental EV Charging Capacity Without Further Voltage Degradation on a Gaborone-Oriented IEEE 69-Bus Surrogate FeederEng · 2026
- Coordinated capacitor-SVG reactive power compensation configuration for substations with high-penetration distributed photovoltaic integrationJournal of Renewable and Sustainable Energy · 2026