Capacity and Operation Planning of Distributed Photovoltaic and Energy Storage with Screening-Based Site Assessment and Coordinated Reactive Power Compensation in Distribution Networks
Yongfeng Yao, Fei Bian, Peizheng Liu, Hao Wang, Shousai Fu, Yi Zhang, Yuanjun Hou
Key points
From the paper's conclusion- Scenario-based planning yields a 0.43% lower observed annualized test cost than deterministic planning on the common 30-day sample, while both satisfy the checked AC limits.
Abstract
High penetration of distributed photovoltaic (PV) generation complicates coordinated PV–energy storage system (ESS) planning and network operation, especially where discrete and continuous reactive-power devices coexist. This study develops a screening-assisted planning–operation framework incorporating capacitor banks (CBs) and static var compensators (SVCs). A time-averaged voltage-stress index (TVSI) and network-loss sensitivity (NLS) identify candidate installation buses. The screened layout A1 is compared with the reference layout A0 at matched PV/ESS ratings under prescribed and coordinated reactive-power control. Under coordinated control, A0 achieves 1.14% lower daily operating cost and 13.17% lower physical voltage deviation than A1; thus, the screened layout is not adopted for subsequent capacity planning. At the retained A0 sites, PV/ESS capacities and seasonal dispatch are jointly optimized using single-level mixed-integer second-order cone programming (MISOCP) with relaxed branch-flow constraints. The formulation includes PV availability and curtailment, ESS state-of-charge dynamics, voltage and branch-current limits, CB configuration-change limits and stage-operation costs, and a unified upstream electricity-purchase boundary. Four-season profiles and probability-weighted PV–load–price scenarios support deterministic and scenario-based planning, with common-input evaluation and independent alternating-current (AC) power-flow verification. In the IEEE 33-bus system, coordinated control reduces A0’s physical voltage-deviation index by 42.96% relative to prescribed control, at a higher daily cost. Scenario-based planning yields a 0.43% lower observed annualized test cost than deterministic planning on the common 30-day sample, while both satisfy the checked AC limits.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Economic Dispatch and Voltage‐Reactive Power Coordinated Control for Active Distribution Networks With Virtual‐Physical Hybrid Energy StorageInternational Transactions on Electrical Energy Systems · 2026
- Uncertainty-aware bilevel energy storage planning for active distribution networks: A fixed-topology DistFlow-based MISOCP framework with voltage-security assessment.PloS one · 2026
- Reliability-oriented optimal planning of photovoltaic distributed generation and energy storage in radial distribution networksResults in Engineering · 2026
- Coordinated Planning of Distribution-Side Distributed Generation and Energy Storage Considering Transmission–Distribution CouplingProcesses · 2026
- Coordinated capacitor-SVG reactive power compensation configuration for substations with high-penetration distributed photovoltaic integrationJournal of Renewable and Sustainable Energy · 2026
- Multi-Objective Planning of Distributed Energy Storage Considering Distribution-Level Electricity Market SimulationEnergies · 2026