Minimal Behavioral Contracts for Compositional Stability of Multi-Vendor Converter-Dominated Power Systems
Jishuo Qin, Fan Li, Taikun Tao, Yuan Si, Hanqing Liang, Guodong Guo
Key points
From the paper's conclusion- With contracts identified from noisy port records of protected models, no frozen decision contradicts the complete-model reference in 2592 compositions of a 49-state benchmark, 244 changed operating conditions, or 171 scenarios of a three-phase electromagnetic-transient benchmark with switching converters.
Abstract
Large converter-dominated power systems combine grid-following (GFL) converters, grid-forming (GFM) converters, and modular multilevel converters (MMCs) from different manufacturers, while complete control models are rarely available to any single operator. This paper asks which terminal information is sufficient for converting separately verified device behavior into a system-level stability statement and shows that this information is irreducible relative to the stated theorems, not in an absolute sense. A minimal behavioral contract is formulated from four constituents: an electrical port convention, a declared operating and frequency domain, an admissible multivariable terminal-dynamic set, and an internal-stability statement; analytical counterexamples show that none of these can be omitted. A network-strength homotopy and a port-level winding number give the exact number of unstable poles, and local integral-quadratic constraints or a structured robust condition then yield a three-way decision (robustly stable, robustly unstable, or undetermined) that accounts for sideband truncation, operating domains, and network uncertainty; exact Schur complements of a sparse bus-level matrix extend it to the complete system, and continuous-frequency covers with closed-form cell bounds replace frequency sampling. With contracts identified from noisy port records of protected models, no frozen decision contradicts the complete-model reference in 2592 compositions of a 49-state benchmark, 244 changed operating conditions, or 171 scenarios of a three-phase electromagnetic-transient benchmark with switching converters. The evidence is model-based and does not replace manufacturer, hardware, or field validation.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- EMT-Validated Branch-and-Bound Determination of Robust Small-Signal Stability Regions for Multi-Converter Power Systems Under Joint Operating, Control, Model-Error and Topological UncertaintyEnergies · 2026
- Unifying Heterogeneous Dissipativity for Distributed Power-System Stability AnalysisarXiv · 2026
- Dynamic System Strength as Structured Stress Radii with Complete Contribution Allocation for Converter-Dominated Multiport GridsElectronics · 2026
- Modular Model Order Reduction for Inverter-Based Power Systems with Stability and Accuracy GuaranteesarXiv · 2026
- Generalized Frequency-Domain Stability Analysis Formulation for Multi-Terminal HVDC SystemsarXiv · 2026
- Digital Implementation of Grid-Forming Control for Power Converters Using Artificial DelaysIEEE/CAA Journal of Automatica Sinica · 2025