Key points
From the paper's conclusion- We reviewed 27 case studies in eight building types (homes, offices, schools, hospitals, industrial halls, data centers, greenhouses and animal houses), twelve of which used simulation, and placed each site in a Köppen–Geiger climate zone.
Abstract
Cooling demand in buildings is rising, met mostly by electric air conditioners. Evaporative cooling uses water instead of a synthetic refrigerant, but its benefit depends on the climate and on how much humidity a building can accept. We reviewed 27 case studies in eight building types (homes, offices, schools, hospitals, industrial halls, data centers, greenhouses and animal houses), twelve of which used simulation, and placed each site in a Köppen–Geiger climate zone. Most studies came from the dry B zones; the other zones contributed only two to four studies each. In dry zones, direct systems were usually enough for greenhouses and animal houses, office workers accepted evaporatively cooled rooms, and an indirect unit cooled a data center without a compressor for 97% of the year. In humid zones (Cfa and Aw), people needed air drying or a compressor as well, but animals and plants still benefited. In the Cfb zone, a hybrid indirect unit cut office electricity use by 45% on the design day. Water use, hygiene and maintenance set the practical limits. We propose a building-type and climate matrix with a confidence rating for each cell and an early-design decision path; most cells rest on one to three studies.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Load-Adaptive Operational Control of an Indirect Evaporative Cooling System for Coordinated Energy and Water Use in a Modular Data Center in a Cold RegionBuildings · 2026
- A TRNSYS-based parametric study of building ventilation systems incorporating Rotary Heat Recovery WheelsApplied Thermal Engineering · 2026
- Role of HVAC in building energy consumption: a critical reviewJournal of Thermal Analysis and Calorimetry · 2026
- When Does Adiabatic Cooling Outperform Dry Cooling? A Twelve-City U.S. Data-Center Siting Assessment at ASHRAE Design Conditions2026
- Thermal mass and cooling demand in a hot-dry commercial building: a controlled 2×2 EnergyPlus case studyCase Studies in Thermal Engineering · 2026
- A Hybrid Physics-Data Decision-Support Framework for Real-Time Prediction and Season-Adaptive Optimization of a Natural Evaporative Water CoolerEngineering Research Express · 2026