Evaluating Resource Isolation for Virtual PLCs: A Full-Factorial Timing Study on an Industrial Edge Platform
Ihsan Altun, Halil Aydoğuş, Kerem Küçük, Onur Gök
Key points
From the paper's conclusion- Adding the NIC claim and its associated interrupt tuning to core isolation reduced mean maximum jitter by a further 6.5%.
Abstract
Predictable control-cycle timing is challenging when virtual programmable logic controllers (vPLCs) share industrial edge resources with computational and communication workloads. The individual and combined benefits of CPU core and network-interface-card (NIC) isolation remain insufficiently characterized beyond maximum-jitter measurements. This study compares four isolation configurations (none, core, NIC, core + NIC) under eight combinations of real-time communication, CPU stress, and non-real-time traffic. A commercial vPLC with a nominal 1 ms cycle was evaluated in 160 one-hour runs (32 scenarios, 576 million cycles). Metrics include per-run maximum positive period jitter (maximum jitter), upper percentiles, and exceedance probabilities. Core isolation was associated with a 75.4% reduction in the grand mean of per-run maximum jitter relative to the unisolated setup. NIC isolation alone lowered this maximum-jitter metric but was associated with more long cycles under real-time load, mainly with CPU stress. Adding the NIC claim and its associated interrupt tuning to core isolation reduced mean maximum jitter by a further 6.5%. Each configuration package bundles a resource claim with kernel and interrupt tuning, so effects cannot be assigned to single mechanisms, and the fixed measurement order limits causal attribution. Lower maxima do not imply better tail behavior; the results are workload-specific associations, not hard real-time guarantees.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Optimization and Evaluation of Container-Based EtherCAT Communication in Virtual PLCsIEEE Transactions on Industrial Electronics · 2026
- Compilation Is Not Correctness: Scan-by-Scan Evaluation of LLM-Generated PLC ProgramsarXiv · 2026
- Trace2ST: Recovering PLC Structured Text from I/O Traces with LLM Generation and VerificationarXiv · 2026
- PLCWorld: Benchmarking LLM-Generated PLC Programs in Closed-Loop Plant SimulationarXiv · 2026
- What Changes with Xenomai 4? An Empirical Study of Real-Time Performance in EtherCAT-Based Robotic ControlApplied Sciences · 2026
- Execution-Time Validation of Context-Carrying Action Intents in Industrial Cyber-Physical SystemsarXiv · 2026