Multi-Objective-Optimization-Based Optimal Sizing of Grid-Following SVG for Enhancing Transient Voltage Stability of Wind Farms Connected to Weak Grids
Yang Kou, Ji Li, Yingli Huo, Weile Liang, Zhi Yuan, Lousong Xu
Key points
From the paper's conclusion- A 10-state PMSG full-converter average-value model predicts recovery time within 1–2 ms of the reduced model for SCR = 1.5–10.0, although the reduced model overestimates post-fault voltage overshoot in very weak grids.
Abstract
When large-scale wind power bases are connected to weak grids, post-fault transient voltage recovery becomes a critical constraint on stable system operation. This paper proposes a multiobjective sizing framework for a grid-following static var generator (SVG) in which a reduced-order RK4 transient model is embedded directly in the capacity decision. The three measurement objectives are post-fault voltage recovery time, SVG investment cost, and system active-power loss, subject to minimum-voltage, recovery-time, and stability constraints. The baseline Pareto set is obtained with NSGA-II, while optimizer dependence is examined against NSGA-III and SMS-EMOA under a common evaluation budget. The grid-strength study is extended to SCR = 1.5–10.0, and the optimization scenarios retain fault-voltage levels of 0.70–0.80 p.u. A separate low-voltage-ride-through (LVRT)-aware wind-turbine model is used to evaluate active-power curtailment, reactive-current priority, and coordinated SVG-wind-turbine support. Under SCR = 2.5 and a retained fault-voltage level of 0.70 p.u., the refined capacity scan shows that enabling wind-turbine reactive support reduces the SVG capacity required to meet the same 0.019 s recovery-time target from 39 to 13 Mvar in the adopted control setting. A 10-state PMSG full-converter average-value model predicts recovery time within 1–2 ms of the reduced model for SCR = 1.5–10.0, although the reduced model overestimates post-fault voltage overshoot in very weak grids. Sequence-domain studies further quantify the additional negative-sequence, DC-link, and rotor-speed stress caused by unbalanced faults. The framework is therefore intended as a planning-stage screening tool rather than a substitute for switching-level electromagnetic-transient verification.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Research on Low Voltage Ride through Capability of Offshore Wind Farm Grid Integration Based on Dynamic Reactive Power CompensationJournal of Engineering Research and Reports · 2026
- Hybrid Reactive Power Compensation Sizing for Grid-Code Compliance of a 120 MW Wind Farm: A Load-Flow Comparison of Passive and STATCOM-Based ConfigurationsEnergies · 2026
- Coordinated Synchronous Condensers and Static Var Generator Planning Considering Unit Commitment-Dependent Multiple Renewable Energy Station Short-Circuit Ratio ConstraintsEnergies · 2026
- Coordinated capacitor-SVG reactive power compensation configuration for substations with high-penetration distributed photovoltaic integrationJournal of Renewable and Sustainable Energy · 2026
- Grid-forming SVG DC-side hybrid capacitor series topology and capacity design methodFrontiers in Energy Research · 2026
- Coordinated Control of IGBT-Based Converters for LVRT Enhancement in Variable-Speed Pumped Storage SystemsMicromachines · 2026