Comprehensive Exergy and Exergoeconomic Analyses and Optimization of a Three-Stage Cascade Refrigeration System Using Environmentally Friendly Refrigerants.
Cenker Aktemur, Ezgi Gurgenc
Department of Mechanical Engineering, Faculty of Engineering and Natural Sciences, Sivas University of Science and Technology, 58000 Sivas, Türkiye. · Department of Mechanical Engineering, Faculty of Technology, Firat University, 23119 Elazig, Türkiye.
Key points
From the paper's conclusion- The findings demonstrate that the refrigerant choice is crucial in achieving better exergetic and exergoeconomic performance for ULTs under various evaporator and condenser conditions.
Abstract
Ultra-low-temperature (ULT) refrigeration systems are widely required in applications such as biomedical storage, cryogenic processing, and advanced scientific facilities, where both exergy efficiency and economic performance are critical. In this study, a comprehensive analysis and optimization of the exergy and exergoeconomic performance evaluation of a triple-stage cascade refrigeration system under ULT refrigeration is presented using ethylene (R1150), ethane (R170), propylene (R1270), difluoroethane (R152a), propane (R290), and fluoroethane (R161). A detailed exergy/exergoeconomic analysis, along with an optimization procedure, is performed at both the overall system level and the component-wise level in order to determine the key performance indicators. Minimizing the total cost product rate for each evaporator and condenser temperature is achieved by optimizing the condensing temperatures of the low-temperature cycle and the medium-temperature cycle. The component-wise analysis reveals that major thermodynamic irreversibilities occur in the HTC compressor and throttling valves, with maximum relative exergy destruction reaching 24.71% in TV-3 and the highest exergy destruction ratio reaching 14.92% in the HTC compressor. From an exergoeconomic perspective, the evaporator exhibits the largest combined exergy destruction and capital investment, and operational and maintenance cost rate (up to 24.73 $/h), while the condenser shows the highest exergoeconomic factor (up to 14.24%). The system-level results show that R1150/R170/R152a has the best exergetic and exergoeconomic performance compared to the other refrigeration combinations within the temperature ranges. Compared with R1150/R170/R290, this combination increases exergy efficiency by up to 5.05% for evaporator temperature variations and up to 7.84% for condenser temperature variations while reducing exergy destruction by up to 7.50% and 11.14%, respectively. Furthermore, the same combination decreases the total exergy destruction cost rate and product cost rate by up to 11.15% and 7.88%, respectively. In contrast, R1150/R170/R290 generally exhibits the poorest overall performance. The findings demonstrate that the refrigerant choice is crucial in achieving better exergetic and exergoeconomic performance for ULTs under various evaporator and condenser conditions.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Thermodynamic Comparison of Two- and Three-Stage Cascade Refrigeration Systems: A Dynamic Energy Assessment in Hospital EnvironmentsEnergies · 2026
- Comparative Assessment of R744-Based Cascade Refrigeration Systems with Advanced Exergy Analysis and Annual Performance Evaluation for Three Turkish CitiesSustainability · 2026
- Thermal performance evaluation of low-GWP refrigerant pairs in cascade refrigeration systems: An experimental and simulation studyInternational Communications in Heat and Mass Transfer · 2026
- Performance evaluation of an ejector-enhanced modified cascade–auto-cascade refrigeration system for ultra-low-temperature coolingProceedings of the Institution of Mechanical Engineers Part E Journal of Process Mechanical Engineering · 2026
- Exergetic and performance assessment of superheated vapor compression refrigeration systems under variable compressor efficiency using conventional and low-GWP refrigerantsInternational Journal of Air-Conditioning and Refrigeration · 2026
- Experimental evaluation of a R290 vapour compression refrigeration system hybridised with a thermoelectric subcoolerEnergy Conversion and Management · 2026