Hot-Dip Galvanized Steel in Fire: Linking NIR/MIR Reflection to Early-Stage Heating Delay Under Standard Fire Exposure
Lukasz Radosinski, Iwona Gajecka, Michał Chmiel, Aleksandra Porebska
Key points
From the paper's conclusion- Thus, from a fire-design perspective, the variability of HDG surface conditions and the resulting uncertainty in its radiative properties may make it difficult to treat galvanized steel as having sufficiently repeatable physical for use in fire safety engineering design or for classification as a certified passive fire-protection system.
Abstract
Hot-dip galvanizing (HDG) protects steel against corrosion, but its influence on heating during fire exposure remains uncertain. This study combines reference-normalized FTIR measurements for five surface conditions with indicative furnace tests for four conditions on HEA 200 steel elements under the EN 1363-1 heating regime. The time to reach 500 °C increased from 570 s for bare steel to 634 s for top-coated HDG, 727 s for polished steel and 773 s for intact HDG. These trends are consistent with reduced radiative absorption by reflective surfaces, while convection continues to supply heat. A section-factor-matched lumped model describes this behaviour through an energy balance combining convective heat transfer and Stefan–Boltzmann radiation. Sensitivity analysis shows that assuming constant low emissivity overpredicts heating delay relative to scenarios in which emissivity increases during exposure. Despite similar initial reflected signals, intact HDG and polished steel exhibited different heating. Thus, from a fire-design perspective, the variability of HDG surface conditions and the resulting uncertainty in its radiative properties may make it difficult to treat galvanized steel as having sufficiently repeatable physical for use in fire safety engineering design or for classification as a certified passive fire-protection system.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Influence of Intumescent Coating Thickness on the Thermal Response of HEA-Profile Steel Columns Under Standard Fire ExposureBuildings · 2026
- Simulation and Optimization of Hydrogen‐Enriched Shaft FurnacecScience · 2025
- Numerical Investigation of Hardfacing Process Parameters for Gate Valve Restoration with Experimental Characterization of Hardfaced SpecimensApplied Mechanics · 2026
- Numerical Investigation of Structural Stress in Ship Cabins with Irregular Breaches Under FireJournal of Marine Science and Engineering · 2026
- Thermomechanical Design of Single-Shear Glulam Connections with Steel Dowels under FireJournal of Physics: Conference Series · 2026
- When the Cable Insulation Burns: Experimental and 2D Modeling Study of Cables with Flame-Retardant Sheaths and Flammable InsulationFire Technology · 2026