Comparative Assessment of Four Mainstream Wind Load Codes/Standards for Transmission Lines and Their Implications for Tower Responses

Ya’nan Tang, Jian Yang, Wenzhe Zheng, Jie Feng, Zhenguo Wang

Key points

From the paper's conclusion
  • This study compares DL/T 5551-2018, ASCE Manual of Practice No.

Abstract

Differences in reference wind conditions and loading formulations complicate comparisons among transmission-line wind-load standards. This study compares DL/T 5551-2018, ASCE Manual of Practice No. 74 (4th ed., 2020), EN 50341-1:2012, and IEC 60826:2017 for a 220-kV double-circuit suspension tower under a common 50-year, 10-min mean wind reference and approximately comparable open-terrain exposures. The tower, conductor, and ground-wire loading expressions are reorganized into a common algebraic framework, and the resulting equivalent static wind loads are applied to a nonlinear static finite element model. For the upper tower panels, relative EN/IEC differences are larger in effective loading multipliers than in height-variation coefficients. Under transverse wind, IEC produces the largest conductor loads, whereas EN produces the largest ground-wire loads. Before adjustment, base overturning moments obtained using ASCE, EN, and IEC are approximately 15–42% higher than those obtained using DL/T across the investigated wind directions. After applying the adopted adjustment factors, DL/T gives the largest tower-top displacement, while base-shear and overturning-moment rankings vary with wind direction. These case-specific findings demonstrate the importance of considering load distributions and multiple response indicators when interpreting differences among the standards.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers