AI-driven ANN-PSO smart-inverter capacity allocation at preselected buses under meteorological uncertainty.
Selman Djeffal, Badreddine Bendriss, Abdelhamid Ghoul, Mohamed Razi Morakchi
Department of Mechanical Engineering, National Polytechnic School of Constantine, Constantine, Algeria. · QUERE Laboratory, Department of Electrical Engineering, Ferhat Abbas University, Setif, Algeria.
Key points
From the paper's conclusion- The tuned ANN achieved an RMSE of 1.6323 kW, an MAE of 1.2314 kW, and an R-squared value of 0.99999. The verified five-start mean-profile solution reduced mean active loss to 15.9900 kW and voltage deviation to 0.051082 p.u., while increasing minimum voltage to 0.98213 p.u. and minimum VSI to 0.96307. Relative to IFLO, the respective improvements were 54.57%, 22.49%, 1.21%, and 8.41%.
Abstract
INTRODUCTION: Radial distribution grids require renewable planning methods that jointly account for meteorological generation, WT/PV capacity allocation, and smart-inverter voltage support. METHODS: An ANN-PSO-VoltVAR framework was developed using 2012-2021 NASA POWER irradiance, wind-speed, and temperature data for In Salah, Algeria. Renewable uncertainty was represented by 12 stratified Weibull-Beta scenarios and an expected-cost/CVaR objective. The mixed decision vector optimized WT units, PV strings, and voltage-dependent inverter support at four preselected IEEE 85-bus locations. An exact backward/forward-sweep module on the standard 33-bus feeder independently verified the load-flow implementation. RESULTS: The tuned ANN achieved an RMSE of 1.6323 kW, an MAE of 1.2314 kW, and an R-squared value of 0.99999. The verified five-start mean-profile solution reduced mean active loss to 15.9900 kW and voltage deviation to 0.051082 p.u., while increasing minimum voltage to 0.98213 p.u. and minimum VSI to 0.96307. Relative to IFLO, the respective improvements were 54.57%, 22.49%, 1.21%, and 8.41%. DISCUSSION: The ablation analysis showed that capacity sizing accounted for most of the loss reduction, whereas Volt-VAR support produced the clearer additional voltage-security gains. Because the IEEE 85-bus electrical response is benchmark-calibrated rather than fully reconstructed, the findings should be interpreted as a reproducible proof-of-concept. Direct full-feeder validation on the IEEE 85-bus system and other networks remains necessary.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Data-Driven Surrogate Modeling for Voltage Security Assessment and EV Hosting Capacity in Solar-Integrated Distribution NetworksAI · 2026
- Integrated machine learning forecasting and grey wolf optimization for optimal operation of virtual power plants in smart distribution networks.Scientific reports · 2026
- Comprehensive assessment of ML-enhanced hybrid RSO–SAO for optimal PV–WT allocation in radial distribution systemsScientific Reports · 2026
- A Digital Engineering Framework for Undervoltage Risk Screening in Renewable-Rich Smart-City Distribution NetworksEnergies · 2026
- A Coordinated Active and Reactive Power Optimization Method for Integrated Energy System Based on an XGBoost Surrogate Model for Voltage Stability MarginElectronics · 2026
- Capacity and Operation Planning of Distributed Photovoltaic and Energy Storage with Screening-Based Site Assessment and Coordinated Reactive Power Compensation in Distribution NetworksEnergies · 2026