PloS one

Detectability of controlled leaks in an Andean water transmission main: A field evaluation of changepoint methods on flow and pressure signals.

Holger Manuel Benavides-Muñoz, Peter Cheung

Research Group "Innovation and Development for the Sustainability of the Urban and Rural Water Cycle", Departamento de Ingeniería Civil, Arquitectura y Geociencias, Universidad Técnica Particular de Loja, Loja, Ecuador. · Faculty of Engineering, Architecture, Urbanism, and Geography, Resan Hydroinformatics Research Laboratory, Universidade Federal de Mato Grosso do Sul, Campo Grande, Mato Grosso do Sul, Brazil.

Key points

From the paper's conclusion
  • We evaluated five unsupervised methods (PELT with Bayesian and Akaike penalties, Bayesian online changepoint detection [BOCD], an OLS-CUSUM structural-break procedure and a moving-average ±3σ chart) on flow and pressure series recorded every 30 s during seven controlled leak trials (valve setting 3-5% of nominal flow) in two field campaigns on an Andean transmission main in Loja, Ecuador.

Abstract

Leak detection on pumped transmission mains that cross steep terrain relies on hydraulic signals whose response to a small leak may be comparable to sensor noise. We evaluated five unsupervised methods (PELT with Bayesian and Akaike penalties, Bayesian online changepoint detection [BOCD], an OLS-CUSUM structural-break procedure and a moving-average ±3σ chart) on flow and pressure series recorded every 30 s during seven controlled leak trials (valve setting 3-5% of nominal flow) in two field campaigns on an Andean transmission main in Loja, Ecuador. Detections were compared with a chance-level reference obtained by placing the same number of changepoints at random. Relative to the preceding leak-free observations, flow decreased in all seven trials (mean -0.50%; sign test p = 0.016; placebo test p = 0.003), whereas pressure, recorded at 0.1-m resolution, showed no change (placebo p = 0.99). No single event exceeded its per-event detection threshold; the flow change was resolvable only as a seven-event mean (signal-to-noise ratio -3.3). None of the five detectors located leak onsets more often than chance (pooled p > 0.40 for every method-signal pair). The PELT variants flagged six of seven events on pressure, but at 560-960 false alarms per day and 13-33% precision. Although BOCD on pressure reached the highest average precision (0.54), its excess over the chance reference was not significant after Holm correction (adjusted p = 0.14). A CUSUM tuned to the observed flow change, the optimal sequential detector for a persistent shift, would need 12-29 min to detect it at one false-alarm per day, 8-20 times the trial duration. Chance-level performance is therefore the expected outcome for 90-120-s leaks at 30-s sampling, whereas a persistent leak producing the same flow change would be detectable within tens of minutes.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Detectability of controlled leaks in an Andean water transmission main: A field evaluation of changepoint methods on flow and pressure signals — Science Skim