High-precision fault inception time detection in active distribution networks using Euclidean distance and Gaussian filtering.
Haiou Cao, Yihua Meng, Chenbin Zhou, Lichen Deng, Jiayan Yu
State Grid Jiangsu Electric Power Company, Nanjing, Jiangsu, China. · State Grid Suzhou Power Supply Company, Suzhou, Jiangsu, China.
Key points
From the paper's conclusion- Combining the advantages of both computational efficiency and detection accuracy, the proposed method demonstrates superior practicality and cost-effectiveness in active distribution networks when compared to existing technologies.
Abstract
Fault signals in power systems often contain high-order harmonics and attenuated oscillations. which pose challenges for traditional fault time detection methods in accurately identifying the fault inception instant. To address this issue, this paper proposes an accurate fault time detection method based on Euclidean distance and Gaussian filter. Based on the phase voltage or current signal of the fault line, the improved high-order Fourier algorithm with attenuation factor is used to fit the curve of the fault phase signal data. The fault signal is compared with the imaginary non-fault signal by using Euclidean distance, and the fitting error is filtered by a Gaussian filtering algorithm to detect the fault segment. Finally, the fault is detected by pixel column, and the fault time is obtained by corresponding the pixel column and time information. The MATLAB/Simulink simulation results and the field test results show that the method can accurately detect the fault time under different harmonics, damped oscillations, transition resistance, short-circuit fault types and sampling rates, and the detection error is basically controlled within 0.1 ms, which achieves high detection accuracy. Combining the advantages of both computational efficiency and detection accuracy, the proposed method demonstrates superior practicality and cost-effectiveness in active distribution networks when compared to existing technologies.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Weak Single Phase-to-Ground Fault Time Detection With Learnable-Parameter-Driven DSP-Enhanced TransformerIEEE Transactions on Smart Grid · 2025
- Fault-Section Location System and Strategy for Single-Phase Ground Faults in Flexible-Grounded Distribution NetworksElectronics · 2026
- Single-phase-to-ground fault detection in distribution networks using learnable spectral filtering and channel covariance attentionAIP Advances · 2026
- Understanding the limits of snapshot-based fault diagnosis in distribution networksarXiv · 2026
- Arc-Fault Detection Using Stage-Wise Alignment and Feature Fusion of Dual Learnable Time-Frequency Representations.Sensors (Basel, Switzerland) · 2026
- Single-Ended Transmission Line Fault Location Based on Multi-Wavelet Time–Frequency Feature Fusion and a Residual Neural NetworkElectronics · 2026