Weak Single Phase-to-Ground Fault Time Detection With Learnable-Parameter-Driven DSP-Enhanced Transformer
Huan Luo, Qiyue Li, Hao Zhou, Wei Sun, Weitao Li, Zhi Liu, Yusheng Ji, Lijian Ding
Hefei University of Technology · University of Science and Technology of China
Key points
From the paper's conclusion- Compared to existing fault detection methods and the state-of-the-art time series anomaly detection models, 2TDformer reduces detection errors by 30%, setting a new benchmark in performance.
Abstract
Accurate location of Single Phase-to-Ground Faults (SPGFs) in Resonantly Grounded Networks is crucial for timely fault clearing, requiring precise dual-time detection of fault initiation and duration. However, existing methods struggle to address the weak and nonlinear characteristics of fault currents. To tackle these challenges, we propose a paradigm that integrates neural networks with enhanced Digital Signal Processing (DSP) method. This approach replaces traditional feature extraction with DSP-based methods and dynamically optimizes DSP parameters through network feedback. Specifically, we introduce a transient weak feature-enhanced attention mechanism and a learnable nonlinear waveform reconstruction mechanism, culminating in a parameter-driven DSP-enhanced Transformer named 2TD-former. Furthermore, we construct a dual-time SPGF detection dataset and publicly release it to facilitate model evaluation and support broader research. Experimental results demonstrate that our method achieves maximum errors of less than 1.4 ms for fault initiation detection and 2.8 ms for duration detection. Compared to existing fault detection methods and the state-of-the-art time series anomaly detection models, 2TDformer reduces detection errors by 30%, setting a new benchmark in performance.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Single-phase-to-ground fault detection in distribution networks using learnable spectral filtering and channel covariance attentionAIP Advances · 2026
- Fault-Section Location System and Strategy for Single-Phase Ground Faults in Flexible-Grounded Distribution NetworksElectronics · 2026
- Arc-Fault Detection Using Stage-Wise Alignment and Feature Fusion of Dual Learnable Time-Frequency Representations.Sensors (Basel, Switzerland) · 2026
- An Improved LSTM Method for Single-Phase Ground Fault Location in Distribution NetworksEnergies · 2026
- Single-Ended Transmission Line Fault Location Based on Multi-Wavelet Time–Frequency Feature Fusion and a Residual Neural NetworkElectronics · 2026
- High-precision fault inception time detection in active distribution networks using Euclidean distance and Gaussian filtering.PloS one · 2026