Ventilation Performance Under Passive Occupancy Conditions: Impacts on IAQ and Cognitive Function in Lecture Halls
Vladanka D. Presburger Ulniković, Aleksandra Milošević Pantović
Key points
From the paper's conclusion- Multiple regression identified CO 2 and occupancy as key predictors of reduced cognitive performance (adjusted R 2 = 0.59).
Abstract
This study investigates the impact of stagnant conditions on indoor air quality (IAQ) and cognitive performance when natural ventilation is not actively managed. Simulating real‐world scenarios where occupants fail to operate windows due to external noise, thermal discomfort, or distraction, measurements were conducted in sealed‐window environments. Data were collected in two distinct lecture halls at University Union–Nikola Tesla, Belgrade: Hall 9 (May 2025, N = 68) and Hall 4 (November 2025, N = 42). Monitored parameters included CO 2 , PM 2.5 , PM 10 , TVOC, HCHO, temperature, and humidity. Under sealed conditions, CO 2 reached 3136 ppm, whereas PM 2.5 peaked at 33 μ g/m 3 , exceeding WHO guidelines. Ventilation calculations identified that window geometry is adequate, yet manual operation is unreliable: achieving the required air exchange would require at least 5 of the 30 tilt windows in Hall 9 to be continuously open (293 window‐minutes per hour). Working memory (digit span backward) showed a strong negative association with CO 2 ( r = −0.75, p < 0.01). Multiple regression identified CO 2 and occupancy as key predictors of reduced cognitive performance (adjusted R 2 = 0.59). Findings demonstrate that although window designs are architecturally sufficient, reliance on manual operation represents a fundamental vulnerability. Automated window actuation or demand‐controlled mechanical ventilation is an effective measure to eliminate occupant‐driven ventilation failure.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Indoor Air Quality and Occupant Perception in an Office Building Adapted for Educational Use: A Zone‐Based Case StudyIndoor Air · 2026
- Desk‐Level CO 2 Sensing for Monitoring Occupancy and Indoor Environmental QualityIndoor Air · 2026
- Mapping Domain-Specific IEQ Exposure-Outcome Pathways: A Systematic Review and Standardized Research Framework of Objective Human Health ResponsesBuildings · 2026
- Experimental and Numerical Insights into Indoor Contaminant Transport and Ventilation Performance: A ReviewEng · 2026
- Indoor air quality in interior architecture studios: Integrating environmental measurements and occupant perceptionsE3S Web of Conferences · 2026
- Intelligent Ventilation and Indoor Air Quality: State of the Art Review (2017–2025)Buildings · 2025