Indoor Air

Ventilation Performance Under Passive Occupancy Conditions: Impacts on IAQ and Cognitive Function in Lecture Halls

Vladanka D. Presburger Ulniković, Aleksandra Milošević Pantović

Key points

From the paper's conclusion
  • Multiple regression identified CO 2 and occupancy as key predictors of reduced cognitive performance (adjusted R 2 = 0.59).

Abstract

This study investigates the impact of stagnant conditions on indoor air quality (IAQ) and cognitive performance when natural ventilation is not actively managed. Simulating real‐world scenarios where occupants fail to operate windows due to external noise, thermal discomfort, or distraction, measurements were conducted in sealed‐window environments. Data were collected in two distinct lecture halls at University Union–Nikola Tesla, Belgrade: Hall 9 (May 2025, N = 68) and Hall 4 (November 2025, N = 42). Monitored parameters included CO 2 , PM 2.5 , PM 10 , TVOC, HCHO, temperature, and humidity. Under sealed conditions, CO 2 reached 3136 ppm, whereas PM 2.5 peaked at 33 μ g/m 3 , exceeding WHO guidelines. Ventilation calculations identified that window geometry is adequate, yet manual operation is unreliable: achieving the required air exchange would require at least 5 of the 30 tilt windows in Hall 9 to be continuously open (293 window‐minutes per hour). Working memory (digit span backward) showed a strong negative association with CO 2 ( r = −0.75, p < 0.01). Multiple regression identified CO 2 and occupancy as key predictors of reduced cognitive performance (adjusted R 2 = 0.59). Findings demonstrate that although window designs are architecturally sufficient, reliance on manual operation represents a fundamental vulnerability. Automated window actuation or demand‐controlled mechanical ventilation is an effective measure to eliminate occupant‐driven ventilation failure.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers