Resilient Distributed Observer-Based Fault-Tolerant Control for Islanded AC Microgrids Subject to Actuator Fault and Saturation Constraints
Sunhua Huang, Yang Zhou, Linyun Xiong, Zhao Yang Dong, Wentao Huang, Fei Gao, Quan Zhou, Xin Li,
City University of Hong Kong · Changsha University of Science and Technology
Key points
From the paper's conclusion- The islanded AC MG with actuator fault and saturation is verified to be predefined-time stable under the proposed DOBDPTFTCs through the Lyapunov theorem.
Abstract
This study presents a novel disturbance observerbased distributed predefined-time fault-tolerant controller (DOBDPTFTC) to achieve precise frequency and voltage regulation, as well as accurate power sharing, in islanded AC MGs subject to actuator fault and saturation constraints. The actuator fault can result in poor performance of the controller, thus degrading the dynamics of the MGs. Predefined-time observers are designed to estimate the disturbances that are caused by the actuator fault within a predefined time. Furthermore, owing to the practical physical limitations of the islanded AC MGs, the output of the actuator will suffer from saturation. The controller saturation is taken into account and a saturation compensation system is designed to remedy the effect of the controller saturation. Besides, the average voltages of all DGs are obtained by a distributed predefined-time observer (DPTO). Then, based on the observations of the disturbances, the DOBDPTFTCs are proposed to guarantee frequency/voltage regulation together with power sharing in a predefined time, which is determined by a tunable parameter. The islanded AC MG with actuator fault and saturation is verified to be predefined-time stable under the proposed DOBDPTFTCs through the Lyapunov theorem. Simulation analysis and hardware-in-the-loop experiments are performed to comprehensively assess the performance of the DOBDPTFTCs in islanded AC MGs.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Predefined‐Time Distributed Adaptive Fault‐Tolerant Voltage Regulation for AC Microgrids With Unknown Actuator FaultsInternational Journal of Adaptive Control and Signal Processing · 2026
- Group Consensus-Based Secondary Control for Islanded AC Microgrids With Communication Link and Actuator Faults.IEEE transactions on cybernetics · 2026
- A deep reinforcement learning-based distributed adaptive fixed-time fault-tolerant control for DC microgrids against actuator faults.ISA transactions · 2026
- Passivity-based fault-tolerant control of onboard skew-symmetric DC microgrids for more electric aircraft: A plug-and-play scheme.ISA transactions · 2026
- Event-triggered adaptive fixed-time sliding mode control for voltage regulation of spacecraft DC microgridsEngineering Research Express · 2026
- Distributed Prescribed-Time Secondary Control for Islanded AC Microgrids Under Communication DelaysIEEE Internet of Things Journal · 2026