Waterborne outbreak of Mycobacterium abscessus in a UK specialist heart and lung hospital 2019-2026: patients, mitigations and implications.
Ellen Heinsbroek, Uta Hill, Olly Allen, Kathy Randall, Caroline Patterson, Iain Roddick, Richard Puleston, Mark Reacher,
Field Service East of England, UK Health Security Agency, Cambridge, United Kingdom. · Royal Papworth Hospital NHS Foundation Trust, Cambridge, United Kingdom.
Key points
From the paper's conclusion- Control measures reduced the incidence of infection but did not eliminate the outbreak strain from the hospital water. Risk mitigation is needed for water systems where vulnerable patients are accommodated.
Abstract
BACKGROUND: Three months after a major cardiothoracic hospital in England relocated to a new building, two cases of Mycobacterium abscessus occurred among lung transplant recipients, triggering an outbreak investigation. METHODS: Respiratory samples were collected from transplant recipients and patients with Cystic Fibrosis (CF) and non-CF bronchiectasis and tested for Mycobacterium abscessus (other patient groups on clinical request). Environmental sampling was undertaken in between 2019 and 2025. Whole genome sequencing (WGS) was performed on clinical and environmental specimens. An outbreak case was defined as a patient with a positive culture matching the strain from water samples on WGS. Epidemiological investigations included assessment of clinical outcomes; calculation of incidence rates; and a case-control study among transplant recipients. RESULTS: Between May 2019 and June 2026, 40 outbreak cases occurred in lung transplant recipients (n=11), patients with CF (n=11) and non-CF bronchiectasis (n=14), and other patient groups (n=4), of which 19 were diagnosed with non-tuberculous mycobacterial pulmonary disease. The case-control study found no specific risk factors associated with lung transplant surgery or bronchoscopy. Environmental sampling showed that the outbreak strain had persisted and disseminated throughout the hospital water system. Following extensive control measures, including point-of-use filters and biocide treatment, incidence fell from 12.8 to 2.2 cases per year. No further case has been identified since June 2025, coinciding with a review of enhanced flushing. CONCLUSIONS: Control measures reduced the incidence of infection but did not eliminate the outbreak strain from the hospital water. Risk mitigation is needed for water systems where vulnerable patients are accommodated.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Hospital Environment–Associated Sources of Mycobacterium abscessus Infection in Transplant RecipientsJAMA Network Open · 2026
- Analysis of nontuberculous mycobacteria infection risks from CDC's water-related healthcare outbreak consultations, 2018-2024.Infection control and hospital epidemiology · 2026
- Hospital Water Safety and Nontuberculous Mycobacteria Risk: A National Evaluation of Organisational Readiness Across NHS Hospitals.The Journal of hospital infection · 2026
- Investigation of Mycobacterium abscessus Cluster in Hospital, Maryland, USA, 2024.Emerging infectious diseases · 2026
- Genomic evidence implicates patient-room showers in Mycobacterium llatzerense bacteremia among two cord blood transplant recipients.Journal of infection and chemotherapy : official journal of the Japan Society of Chemotherapy · 2026
- Silent bronchoscopy-associated outbreak of Stenotrophomonas maltophilia and pseudo-outbreak of Mycobacterium gordonae linked to contaminated rinse water and a damaged bronchoscope.American journal of infection control · 2026