Spatial propagation structure guided grouped weighted prediction error dereverberation algorithm for partial discharge acoustic localization
Zhenghong Xiao, Bo Lin
Key points
From the paper's conclusion- To address this issue, this paper proposes a spatial propagation structure guided grouped weighted prediction error (WPE) (SPS-GWPE) algorithm for multichannel dereverberation before acoustic source localization.
Abstract
Partial discharge (PD) acoustic source localization provides a non-contact approach for identifying insulation defects in high-voltage electrical equipment. However, acoustic reverberation in enclosed and practical environments can spread the time–frequency characteristics of PD impulses and affect the inter-channel spatial information required for localization. To address this issue, this paper proposes a spatial propagation structure guided grouped weighted prediction error (WPE) (SPS-GWPE) algorithm for multichannel dereverberation before acoustic source localization. First, inter-channel relative arrival-time differences are used to construct spatial propagation structure vectors, and density-based clustering is employed to identify reliable direct-path PD impulses. Subsequently, the large-scale microphone array is divided into multiple subarrays to reduce the computational dimension of the WPE prediction filter and improve numerical stability under sparse impulse observations. Furthermore, a pulse-preservation mechanism together with a global variance-sharing strategy within direct-path regions is introduced to prevent direct-path PD impulses from being incorrectly modeled as predictable reverberation while maintaining amplitude and phase consistency across different subarrays. The de-reverberated signals are subsequently processed using the multisnapshot Newtonized orthogonal matching pursuit algorithm for source localization. Simulation and experimental results show that SPS-GWPE can suppress part of the reverberation while preserving the main direct-path characteristics of PD signals, thereby reducing spurious localization responses and improving localization performance under reverberant conditions. The proposed method provides an interpretable model-driven framework for acoustic localization of PD sources in complex acoustic environments.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Partial Discharge Detection and Localization in Power Transformers Using an Integrated Fiber‐Optic Acoustic Monitoring FrameworkJournal of Sensors · 2026
- Research on partial discharge signal recognition and classification of power transformer based on acoustic-VMD and CNN-LSTMPLoS ONE · 2025
- Optical fiber sensing and partial discharge fault diagnosis for power cable health monitoringMeasurement Science and Technology · 2025
- Transformer partial discharge location method based on time delay compensation and improved artificial lemming algorithm.The Review of scientific instruments · 2026
- Quasi-Distributed Partial Discharge Monitoring System with Remote Demodulation Based on DFB-FL/Interferometer Hybrid Sensing.Nanomaterials (Basel, Switzerland) · 2026
- Study on Acoustic Emission Signals Generated by Partial Discharges Under DC StressSensors · 2026