Design of dynamic and thermal stability test system for UHV switchgear based on 330kV grid power supply

Zhilin Kang, Yulin Kang, Jianzhen An, Shuqi Ling, Xuefu Kang, Shiping Wang

Key points

From the paper's conclusion
  • To meet the low-voltage, high-current, and long-duration requirements of thermal and dynamic stability tests for UHV disconnectors and earthing switches, this paper proposes a two-stage step-down test system powered by a 330 kV grid.

Abstract

To meet the low-voltage, high-current, and long-duration requirements of thermal and dynamic stability tests for UHV disconnectors and earthing switches, this paper proposes a two-stage step-down test system powered by a 330 kV grid. The system employs a 12.5 MVA transformer (330 kV/35 kV) and a 90 MVA short-time-rated low-voltage high-current transformer (35 kV/0.206–0.824 kV). A seven-level binary reactor (0–254 Ω, 2 Ω step) enables continuous impedance matching, a phase-selective synchronous closing device (±3.6° accuracy) suppresses DC components within 20%, and a 35 kV/31.5 kA circuit breaker performs centralized interruption. A unified low-voltage-side impedance model is established and all operating conditions are quantitatively verified. Tests on a GW45–800 kV disconnector (170 kA/0.3 s peak, 63.3 kA/2 s short-time) show excellent agreement with calculations, confirming system practicality.