Design of dynamic and thermal stability test system for UHV switchgear based on 330kV grid power supply
Zhilin Kang, Yulin Kang, Jianzhen An, Shuqi Ling, Xuefu Kang, Shiping Wang
Key points
From the paper's conclusion- To meet the low-voltage, high-current, and long-duration requirements of thermal and dynamic stability tests for UHV disconnectors and earthing switches, this paper proposes a two-stage step-down test system powered by a 330 kV grid.
Abstract
To meet the low-voltage, high-current, and long-duration requirements of thermal and dynamic stability tests for UHV disconnectors and earthing switches, this paper proposes a two-stage step-down test system powered by a 330 kV grid. The system employs a 12.5 MVA transformer (330 kV/35 kV) and a 90 MVA short-time-rated low-voltage high-current transformer (35 kV/0.206–0.824 kV). A seven-level binary reactor (0–254 Ω, 2 Ω step) enables continuous impedance matching, a phase-selective synchronous closing device (±3.6° accuracy) suppresses DC components within 20%, and a 35 kV/31.5 kA circuit breaker performs centralized interruption. A unified low-voltage-side impedance model is established and all operating conditions are quantitatively verified. Tests on a GW45–800 kV disconnector (170 kA/0.3 s peak, 63.3 kA/2 s short-time) show excellent agreement with calculations, confirming system practicality.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Short‐Circuit Current Behavior in High‐Voltage Disconnectors: A Critical Review of Analytical, Numerical, and Experimental InvestigationsRadio Science · 2026
- Technical Innovation Assessment of SiC Varistors for Quench Protection of DEMO Toroidal Field Superconducting CoilsSuperconductor Science and Technology · 2026
- Investigation on Electromagnetic–Thermal–Mechanical Multi-Physics Field Characteristics of GIS Disconnector Under Different Contact ConditionsEnergies · 2026
- Modeling and Applicability of Nonlinear RDDS for Controlled Closing of 550 kV SF6 Circuit BreakersEnergies · 2026
- Seismic Performance and Reinforcement Strategies for ±600 kV Suspended Converter Valves — Part1: Seismic VulnerabilitiesSAE technical papers on CD-ROM/SAE technical paper series · 2026
- Voltage-Disturbance Identification and Fast Transfer Control of an IGCT-Based Hybrid Solid-State Transfer Switch.Sensors (Basel, Switzerland) · 2026