Design and electric field analysis of a novel large-capacity wide-range adjustable shunt reactor
Yanming Cao, Juzhen Wu, Kanghang He, Zheng Wei, Guijuan Wang, Hu Luo, Li Peng, Jingyu Yang
Key points
From the paper's conclusion- Against this background, this paper proposes a novel design scheme of a large-capacity wide-range adjustable shunt reactor suitable for the 220 kV voltage level.
Abstract
Shunt reactors play a critical role in high-voltage, long-distance power transmission and transformation systems. They are mainly employed to compensate for the capacitive effects of transmission lines, reduce line losses, and effectively maintain reactive power balance within the system. With the integration of large-scale renewable energy such as wind power and photovoltaic power into the power grid, the system operation mode has become increasingly complex, the requirement for flexibility in reactive power regulation has been continuously improved, and the demand for adjustable shunt reactors has become increasingly prominent. Against this background, this paper proposes a novel design scheme of a large-capacity wide-range adjustable shunt reactor suitable for the 220 kV voltage level. First, to achieve fast and continuous adjustment of the reactance value in the range of 100%–14%, an innovative five-winding structure design is proposed, which significantly enhances the reactive power regulation capability and system adaptability. Second, the overvoltage distribution characteristics under lightning impulse and power frequency withstand voltage conditions are focused on, ensuring sufficient insulation margin and reasonably controlling the voltage stress borne by switchgear. Then, to ensure insulation safety under high voltage levels, dielectric property tests of insulation components are carried out, revealing the influence laws of moisture content, temperature, and frequency on relative permittivity and conductivity. Finally, an electric field simulation model of the reactor is established based on the finite element method. Under different operating conditions of temperature, moisture content, and frequency, the electric field distribution in key areas is calculated and verified.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Hybrid Reactive Power Compensation Sizing for Grid-Code Compliance of a 120 MW Wind Farm: A Load-Flow Comparison of Passive and STATCOM-Based ConfigurationsEnergies · 2026
- Research on Partial Discharge Signal Propagation Characteristics of UHV Core Reactor and Optimization of Measuring Points on Oil Tank WallIEEJ Transactions on Electrical and Electronic Engineering · 2026
- Type Tests of a 10 kV/1 MVar High-Temperature Superconducting Air-Core Shunt ReactorIEEE Transactions on Applied Superconductivity · 2026
- Reactive power reserve-constrained optimal reactive power dispatch for enhanced voltage stabilityEnergy Reports · 2025
- Research on Wind-Induced Fatigue of Substation Disconnect Switchgear StructuresEnergies · 2026
- Integrated Insulation Coordination for Pollution- and Lightning-Exposed Medium-Voltage Distribution NetworksEng · 2026