Aftercooling of district heating: Performance of substations with cascading concepts

Daniel Rye, Liv Lorentzen, Donya Sheikh Khan, Christian Anker Hviid

Key points

From the paper's conclusion
  • The results show that substations with a single cascade generally performed better than conventional designs, while double-cascade substations provided even greater improvement.

Abstract

The use of district heating (DH) is a key technology for a sustainable future, but its efficiency depends on the performance of the local DH substations. Conventional DH substations operate with separate flows for space heating (SH) and domestic hot water (DHW). This study investigates alternative configurations in which SH return flow is cascaded to DHW and vice versa, with the aim of reducing the overall return temperature of the DH flow. Conventional and cascaded substation designs were modelled and simulated using real operational data, and their performances were compared based on their flow-weighted return temperatures. The results show that substations with a single cascade generally performed better than conventional designs, while double-cascade substations provided even greater improvement. Additionally, DHW production efficiency was significantly improved by combining a plate heat exchanger with a single hot water tank. Seasonal variations strongly influenced performance, with return temperature reductions from 1.6 to 3.2 °C in a February week and up to 8.5 to 9.5 °C in a July week (no cascade in July week was possible, since there was no SH demand), compared with conventional DH substations. However, additional cascades result in higher pressure drops, which may pose challenges during peak demand.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers