Simultaneous Dissolved Gas Analysis in Transformer Oil via Time-Division-Multiplexed Quartz-Enhanced Photoacoustic Spectroscopy
Jialiang Dai, Yixin Zhang, Jiapeng Wang, Chenglong Wang, Y. Wang, Qingyuan Tian, Y. H. Chen, Chaofan Feng,
Shanxi University of Traditional Chinese Medicine · Xidian University
Key points
From the paper's conclusion- We report for the first time a time-division-multiplexed quartz-enhanced photoacoustic spectroscopy (QEPAS) sensing system capable of simultaneously and sensitively detecting dissolved C 2 H 2 and CH 4, even with an extremely small amount of required sample gas.
Abstract
Dissolved gas analysis (DGA) is an essential method for monitoring and diagnosing faults in oil-immersed transformers. Acetylene (C 2 H 2 ) and methane (CH 4 ) are key indicator gases for fault identification. We report for the first time a time-division-multiplexed quartz-enhanced photoacoustic spectroscopy (QEPAS) sensing system capable of simultaneously and sensitively detecting dissolved C 2 H 2 and CH 4, even with an extremely small amount of required sample gas. The on-beam configuration enhanced the 2 f signal amplitude by nearly 20-fold. The sensing system achieved minimum detection limits (MDLs) of approximately 15 ppb for C 2 H 2 and 0.3 ppm for CH 4, which are 2–3 orders of magnitude lower than the safety thresholds defined in the relevant industry standards. The detectability of the sensing system satisfies the requirements for DGA in transformer oil. With a gas cell volume of approximately 1.6 mL, the system markedly reduces the required oil sample volume. By integrating headspace degassing with QEPAS, the sensing system enables real-time monitoring and analysis of the oil-gas equilibrium behavior of dissolved C 2 H 2 and CH 4 . With its high sensitivity, rapid response, and low sample consumption, the proposed sensing system provides a viable and efficient approach for early detection of transformer faults. Furthermore, it establishes a foundation for applying QEPAS to dissolved gas analysis in transformer oil.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Research progress of online monitoring techniques for dissolved gas analysis in insulating oilFrontiers in Chemistry · 2025
- Ni-Doped PtSe₂ for Dissolved Gas Detection in Transformer Oil: A First-Principles StudyInternational Journal of Pattern Recognition and Artificial Intelligence · 2026
- Simultaneous Detection of Hydrogen and Acetylene Using a Photoacoustic Gas Sensor Based on Frequency Tracking and WMS-2 f TechniqueAnalytical Chemistry · 2025
- On–off-beam differential resonance quartz-enhanced photoacoustic spectroscopy gas sensing technologyOptics Letters · 2026
- Influence of High‐Altitude Environment on Detection of Dissolved Gases in Oil Based on Photoacoustic SpectroscopyMicrowave and Optical Technology Letters · 2026
- Comparative Study on Sensing Properties of the PdSe₂ –CdS Heterojunction and Pd-Modified PdSe₂ –CdS for Dissolved Gases in Transformer Oil Based on Density Functional Theory CalculationsLangmuir · 2026