Energy, exergy, and environmental analysis of five low-GWP refrigerants considered as alternatives to R410A for air conditioning systems
Ali M. Ashour, Hayder Mohsin Ali, Saif Ali Kadhim, Karrar A. Hammoodi, Farhan Lafta Rashid, Ravishankar Sathyamurthy, Abdallah Bouabidi
University of Technology - Iraq · University of Al Maarif
Key points
From the paper's conclusion- This study undertakes a comprehensive energy, exergy, and environmental analysis of five low-GWP refrigerants R32, R290, R454B, R454C, and R513A to be used as alternatives to R410A.
Abstract
Abstract The sustainability concern of high Global Warming Potential (GWP) refrigerants like R410A has spurred universal efforts in searching for low-GWP replacements in vapor-compression air conditioning systems. This study undertakes a comprehensive energy, exergy, and environmental analysis of five low-GWP refrigerants R32, R290, R454B, R454C, and R513A to be used as alternatives to R410A. A model of a single-stage vapor compression cycle was constructed and simulated with Engineering Equation Solver (EES) with real fluid property data under steady-state conditions. Simulation was undertaken using evaporating temperatures of –5 °C to 5 °C and condensing temperatures of 30 °C to 50 °C with fixed subcooling (5 K) and superheat (7 K) values. To maintain accuracy and credibility, the model was checked against literature data of experiments under similar working conditions with deviation of less than 10% in mass flow rate, discharge temperature, cooling capacity, power to compressor, and Coefficient of Performance (COP). From the analysis, it is found that R290 has the best thermodynamic performance with an optimal COP value of 7.91, 5.6% better than R410A and an optimal cooling capacity of 4.30 kW, 19.3% greater than R410A. It achieves the highest exergy efficiency of 0.52 and the lowest exergy destruction in components. R454B, with slightly lower COP performance, has the lowest Total Equivalent Warming Impact (TEWI) of 13.3 tons CO₂, which is some 16% less than R410A. On the other hand, R454C has the highest exergy destruction of 120.4 W and TEWI of 18.4 tons CO₂. R290 and R454B are thus found to be the best low-GWP options to fulfill the transition to environment-friendly and energy-efficient air conditioning systems.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Experimental investigation of split air conditioning unit: exergy and total equivalent warming impact analysis using R32 and R290 instead of refrigerant R410AInternational Journal of Air-Conditioning and Refrigeration · 2026
- Combined Thermodynamic and Environmental Impact Assessment of Environmentally Preferable Refrigerants Used for Water Heaters Based on Water-to-Water Heat PumpThermo · 2026
- Exergetic and performance assessment of superheated vapor compression refrigeration systems under variable compressor efficiency using conventional and low-GWP refrigerantsInternational Journal of Air-Conditioning and Refrigeration · 2026
- Energy and Exergy Analysis of Recuperative Organic Rankine Cycle for Six Low-GWP RefrigerantsSciEn Conference Series Engineering · 2026
- Experimental Study on the Performance of a Vapor Compression Refrigeration System Using Alternative RefrigerantsASIAN JOURNAL OF CONVERGENCE IN TECHNOLOGY · 2025
- Thermal performance evaluation of low-GWP refrigerant pairs in cascade refrigeration systems: An experimental and simulation studyInternational Communications in Heat and Mass Transfer · 2026