Frequency-Security-Aware Real-Time Economic Dispatch with Data Center UPS Flexibility for Inertia and Primary Frequency Response Services
Shengyi Wang, Liang Du
Key points
From the paper's conclusion- Numerical validation on a modified IEEE 39-bus system demonstrates that the proposed RTED model with UPS flexibility can economically support system operation and significantly improve frequency security under active-power deficit disturbances.
Abstract
The increasing penetration of renewable energy and the rapid growth of AI data centers are introducing significant challenges to power system frequency security. There is an urgent need to identify grid-compatible resources capable of providing fast frequency support. This paper proposes a frequency-security-aware real-time economic dispatch (RTED) model that enables data center (DC) uninterruptible power supply (UPS) systems to provide steady-state power balancing, inertia response, and primary frequency response (PFR) services. Specifically, tractable analytical frequency-security constraints are derived and incorporated into the RTED framework through second-order cone programming (SOCP) formulation. The proposed model jointly optimizes energy, reserve, and inertia to minimize system operation cost while preventing under-frequency load shedding (UFLS). Numerical validation on a modified IEEE 39-bus system demonstrates that the proposed RTED model with UPS flexibility can economically support system operation and significantly improve frequency security under active-power deficit disturbances.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Hyperscale Data Centers as Wide-Area Damping Actuators for Low-Inertia Power SystemsarXiv · 2026
- Aggregation Model and Market Mechanism for Virtual Power Plant Participation in Inertia and Primary Frequency ResponseIEEE Transactions on Power Systems · 2025
- Physics-Guided Multi-Output Surrogate Modeling of a Centralized-UPS Data CenterarXiv · 2026
- Dynamic Modeling of Transmission Networks, Grid-Following Inverters, and UPS-Based AI Data CentersarXiv · 2026
- Data Center Oscillation Isolation and Grid Support: Fundamental Limits and Source-Selective ControlarXiv · 2026
- AI Data Centers Meet Electrical Grids: A Review of Power Challenges and Coordinated SolutionsarXiv · 2026