Sub-Synchronous Control Interaction Risk of Large Data Center Loads: A Frequency-Scan Assessment with Cross-Model Validation
Salish Maharjan, Junyuan Zheng, Lung-An Lee, Min Lwin, Zhaoyu Wang
Key points
From the paper's conclusion- We then repeat the scans on three public models from PNNL, TAMU, and NLR.
Abstract
Data centers are now one of the fastest-growing loads on the bulk power system, and most of their demand reaches the grid through power converters inside uninterruptible power supplies (UPS). Whether these loads can take part in sub-synchronous control interaction (SSCI), as wind and HVDC converters do, has not been studied extensively. We examine this question with impedance-based frequency scans at the point of common coupling (PCC). Using a detailed proprietary model (INS-ISU), we scan the motor, variable-frequency-drive (VFD), lighting, and UPS-fed information-technology (IT) branches of a representative facility separately. Only the UPS in double-conversion mode shows negative resistance; it covers the whole sub-synchronous band and continues up to about 170 Hz. The other branches, and the UPS in bypass mode, stay passive. We then repeat the scans on three public models from PNNL, TAMU, and NLR. None of them shows negative resistance in bypass mode, while three of the four models do in double-conversion mode. Lowering the load from rated to light load makes the negative resistance deeper, as expected for a constant-power load, so a lightly loaded facility in double-conversion mode is the worst case. Raising the UPS DC-link capacitance pushes the negative resistance into a narrow band around the fundamental. These findings give a basis for screening data centers for SSCI during interconnection studies.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Physics-Guided Multi-Output Surrogate Modeling of a Centralized-UPS Data CenterarXiv · 2026
- Hyperscale Data Centers as Wide-Area Damping Actuators for Low-Inertia Power SystemsarXiv · 2026
- Data Center Oscillation Isolation and Grid Support: Fundamental Limits and Source-Selective ControlarXiv · 2026
- EMT Modeling and Coordinated Mode-Transition Ride-Through Control of Modern Data CentersarXiv · 2026
- Open-Source Multi-Fidelity EMT Modeling of Data Center Loads for Power System StudiesarXiv · 2026
- A Dynamic Model and Stability Analysis of a Grid-Interactive Data CenterarXiv · 2026