Assessing Data Center Hosting Capacity Considering Electromagnetic Transient Dynamics
Fan Jiang, Xingpeng Li
Key points
From the paper's conclusion- Thus, the dynamic response of the data center and the grid should be part of the hosting capacity assessment, and the comparison of connection locations should be made on the post-outage dynamic capacity.
Abstract
Hosting capacity is commonly assessed with steady-state optimization, which leaves the dynamic response of the data center and the grid at the resulting operating point untested. This paper assesses candidate data center capacities by coupling a unit commitment (UC) model with electromagnetic transient (EMT) simulation. During the capacity search, the UC model determines the economic dispatch for each tested data center capacity, and the resulting operating points are tested for settling with the generators committed online by the UC model and after a selected synchronous generator outage. Three nested capacities are obtained: the optimization-based steady-state capacity, the dynamic pre-outage capacity, and the post-outage dynamic capacity, each bounded by the previous one. On a test system with a detailed data center model, both dynamic capacities fall well below the optimization capacity, and the ranking of connection locations changes with the assessment stage and with the outage. In the most severe outage case at each candidate bus, the capacity is about 30% below the steady-state capacity. Thus, the dynamic response of the data center and the grid should be part of the hosting capacity assessment, and the comparison of connection locations should be made on the post-outage dynamic capacity.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- A Dynamic Model and Stability Analysis of a Grid-Interactive Data CenterarXiv · 2026
- N-1 Security constrained Hosting Capacity Assessment for Ultra Large-scale Data Center with Workload FlexibilityarXiv · 2026
- Data Center Oscillation Isolation and Grid Support: Fundamental Limits and Source-Selective ControlarXiv · 2026
- Modeling and Stability of Power Systems With Coupled Data Center and Grid DynamicsarXiv · 2026
- U.S. Data Center Growth Through 2030: A Critical Review of Grid Adequacy and Transmission Expansion PlanningarXiv · 2026
- Oscillation assessment of the KPG-193 test system with hyperscale data center interconnectionsInternational Journal of Electrical Power & Energy Systems · 2026