An Accurate Modulation-Assisted Method for Phasor Estimation Under Decaying DC Offsets
Sina Mohammadi, Apurv Shukla, Junho Hong, Wencong Su
Key points
From the paper's conclusion- Decaying DC (DDC) offsets severely compromise the accurate estimation of current phasors immediately following power grid fault occurrence.
Abstract
Decaying DC (DDC) offsets severely compromise the accurate estimation of current phasors immediately following power grid fault occurrence. Consequently, conventional full-cycle discrete Fourier transform (FCDFT) algorithms experience decaying oscillatory magnitude errors, potentially causing distance relays to malfunction. This paper introduces a modulation-assisted technique designed to precisely eliminate the DDC components from fault current signals. By multiplying the fault signal with a high-frequency carrier and applying consecutive sliding Fourier projections, the proposed method effectively isolates the DDC signal while entirely rejecting higher-order harmonic interference. It utilizes a direct algebraic solution derived from a robust forward-difference operation across just three sequential projections to estimate and extract the DDC parameters. Furthermore, the algorithm seamlessly processes both single and multiple DDC components by dynamically tracking them as one equivalent first-order mode. Extensive evaluations are conducted to validate the proposed method accuracy. The proposed algorithm limits the maximum overshoot (MO) to 0.62% (0.59% for $k \geq 8$) for the evaluated DDC cases, and to 2.47% (0.95% at 20 dB for $k = 8$) under noisy conditions.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Transformer-guided Variable Projection for Phasor and Fault-Time Estimation Under DDC OffsetarXiv · 2026
- Fast Dielectric Loss Angle Estimation Method in Harmonic and Noisy EnvironmentsElectronics · 2026
- Does Synchrophasor Attenuation Preclude Detection of High-Frequency Oscillations?arXiv · 2026
- A Frequency-Fixed Dual Third-Order Generalized Integrator PLL with Complex Rotation Compensation for Three-Phase Grid SynchronizationEnergies · 2026
- On PMU Adequacy for Wideband Dynamics Tracking Beyond Attenuation AssumptionsarXiv · 2026
- Power Quality Improvement of DSTATCOM Using Fast Hybrid-PLL-Based Control Method for Wind Energy ApplicationsProtection and Control of Modern Power Systems · 2026