From Caveman to COBA: Coordinated Optimization-Based Attacks on Grid-Edge Smart Inverters in DER-Rich Power Systems
Emad Abukhousa, Anna Raymaker, Animesh Chhotaray, Daniel Molzahn, Saman Zonouz, Sakis Meliopoulos
Key points
From the paper's conclusion- The results show that topology, target selection, and command capability determine DER-induced thermal risk beyond aggregate penetration alone.
Abstract
Aggregation platforms and smart-inverter control channels can allow a compromised coordination layer to alter active- and reactive-power commands across a geographically distributed DER fleet. This paper introduces the Coordinated Optimization-Based Attack (COBA), which uses network information and location-specific DER P/Q setpoints to maximize thermal loading on a selected transmission corridor. COBA is compared with low-information CAV baselines limited to a single uniform fleet command: all-off, all-on, maximum reactive absorption, or maximum reactive injection. The Hawaii Synthetic Grid-37 Buses case is evaluated with rooftop-photovoltaic-like capability aggregated at 20 selected 69-kV buses and verified using MATPOWER power flow. Under the case's single-reference-bus balancing convention, COBA overloads B86 (WAIALUA69-WAIANAE69) near 30% penetration and B51 (COCONUT69-PALM69) near 55%, while same-target uniform loadings remain lower and uniform commands primarily stress other natural weak lines. The results show that topology, target selection, and command capability determine DER-induced thermal risk beyond aggregate penetration alone.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Checking DER Commands Against Grid Context Catches Credentialed Attacks Static Checks MissarXiv · 2026
- Minimizing Risk of Load Redistribution Attacks on Electric Grids in the Presence of Insider Threats.Risk analysis : an official publication of the Society for Risk Analysis · 2026
- A Critical Review of Interface-Centered Cybersecurity for Distributed Energy Resource Systems: Protocol Semantics, Attack Detection, and RecoveryElectronics · 2026
- Adaptive Robust Planner-Attacker-Operator Model Against Multistage Uncertain Malicious Attacks for Power Systems With Volatile Wind PowerIEEE Transactions on Industrial Informatics · 2026
- Hierarchical Dispatch of Multi-type Virtual Power Plants for Enhancing Resilience of Power Systems Under WildfiresJournal of Modern Power Systems and Clean Energy · 2026
- Photovoltaic Inverters as Grid-Balancing Actuators: A Constraint-Stack Review of Controllability, Interoperability, and AggregationEnergies · 2026