One Agent per Zone: Decentralised Active Inference under Partial Observability for Multi-Zone HVAC Control on Edge Hardware
Panagiotis Kasnesis, Lazaros Toumanidis, Christos Chatzigeorgiou, Amalia Contiero Syropoulou, Miguel De Prado
Key points
From the paper's conclusion- The whole fleet runs on a single low-cost Raspberry Pi 5, closing the observation-to-action loop over MQTT in 442 ms at p95, far below the 15-minute control step.
Abstract
Multi-zone HVAC control is a shared-resource problem: zones on a floor share one fan and cooling coil, so each zone's demand affects its neighbours and the building's peak power. One controller per zone scales well and isolates faults, but each controller then observes only its own zone, not the shared air loop. In this work, we present a decentralised controller that assigns each zone an independent active-inference agent, which plans by minimising expected free energy and learns its zone dynamics online. The agents exchange no messages, so none depends on peers or a coordinator; each accounts for the unobserved coupling through a latent disturbance and a congestion signal derived from the metered power of the other floors. Fifteen agents are evaluated in EnergyPlus on a Sinergym office building against three rule-based controllers and three MADDPG fleets, one given the same floor meters. On five noisy weather years unseen during training, the fleet attains the lowest mean building peak (88.3 kW, 3 to 17 % below the baselines) and staggers the floor peaks better than any baseline, with a coincidence factor (building peak over the sum of the floor peaks) of 0.929 versus 0.936 to 0.994. Compared with a reactive rule at similar comfort (0.912 versus 0.916), it lowers the sum of monthly peaks, on which demand charges are billed, by 33 kW (4 %) in every year, at the cost of about 10 % more energy. It costs 9% less per year than the proactive rule (at lower comfort) and 1% less than the MADDPG fleet given the same floor meters, in every test year. The whole fleet runs on a single low-cost Raspberry Pi 5, closing the observation-to-action loop over MQTT in 442 ms at p95, far below the 15-minute control step.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- From Data to Valves: A Self-Learning, Production-Grade Edge Stack for Sustainable HVAC ControlarXiv · 2026
- Delay-Aware Temporal Action Embedding for Deep Reinforcement Learning-Based HVAC System ControlACM Transactions on Sensor Networks · 2026
- Online Identification Can Replace a Floor-Plan Prior on Unseen BuildingsarXiv · 2026
- When does deep reinforcement learning pay off in HVAC supervisory control? Four small Modelica case studies trained directly on FMUsarXiv · 2026
- Improving Building Energy Efficiency with an Indoor Environmental World Model and Counterfactual Adaptive LearningarXiv · 2026
- A Hybrid LSTM–PPO–RBC Edge Controller for Building HVAC: Sim-to-Real Validation on a Raspberry Pi 4Energies · 2026