Journal of visualized experiments : JoVE

Machine Learning-Based Classification of Overload Conditions In Smart Grids Using Multi-Source Electrical and Environmental Features.

Kanaka Raju Kalla, Bharat Kumar Chigilipalli, A Madhuri, Aparna Chaparala, Ch V V Ramana, Fahad R Albogamy, Samih M Mostafa

Department of Electrical and Electronics Engineering, Aditya Institute of Technology and Management; kallakanakaraju@gmail.com. · Department of Mechanical Engineering, Vignan's Institute of Information Technology (A).

Computational

Key points

From the paper's conclusion
  • Overall, the combination of physics-inspired feature engineering, temporal model validation, and explainable machine learning provided an effective approach for data-driven smart-grid overload detection.

Abstract

Smart-grid overload detection is essential for identifying abnormal operating conditions and supporting reliable grid monitoring. A machine-learning-based framework was developed to distinguish normal and overloaded operating states using electrical, renewable-generation, environmental, and operational measurements. A time-ordered dataset comprising 50,000 observations sampled at 15 min intervals from January 1, 2024, to June 4, 2025, was analyzed, with overload events representing 10% of the observations. Physics-inspired features were constructed to characterize apparent power, reactive loading, renewable contribution, grid dependence, load-supply imbalance, voltage deviation, and power-factor stress. Six classifiers-logistic regression, support vector machine, random forest, gradient-boosted decision trees, and two additional gradient-boosting classifiers-were comparatively evaluated using a chronological 70:15:15 training-validation-testing strategy. The strongest baseline model achieved a validation F1-score of 0.7497. During five-fold temporal cross-validation, the best configuration achieved an aggregated F1-score of 0.78363, whereas the selected model achieved an F1-score of 0.75129 on the separate chronological validation set. The optimized model was retrained using the combined training and validation data and evaluated on an independent test set of 7,500 observations. The model achieved 95.63% accuracy, 78.96% precision, 93.71% recall, an F1-score of 85.70%, a receiver operating characteristic area under the curve of 99.12%, a precision-recall area under the curve of 95.10%, a Matthews correlation coefficient of 83.57%, and Cohen's κ of 83.14%. The confusion matrix indicated 983 true-positive overload events, 66 false-negative events, and 262 false-positive events. Feature-attribution analysis identified grid supply, solar power, predicted load, and power consumption as the dominant predictors and revealed nonlinear feature interactions. Overall, the combination of physics-inspired feature engineering, temporal model validation, and explainable machine learning provided an effective approach for data-driven smart-grid overload detection.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Machine Learning-Based Classification of Overload Conditions In Smart Grids Using Multi-Source Electrical and Environmental Features — Science Skim