A Closed-Loop Measurement Study of Runtime Governance in AI-Driven Smart Building Climate Control.
Norkobil Saydirasulov Saydirasulovich, Dilmurod Abdujalilovich Davronbekov, Makhmudov Makhsum Mubashirovich, Young Im Cho
Department of Computer Engineering, Gachon University, Sujeong-gu, Seongnam-si 461-701, Gyeonggi-do, Republic of Korea. · Department of Technologies of Mobile Communication, Tashkent University of Information Technologies Named After Muhammad Al-Khwarizmi, Tashkent 100084, Uzbekistan.
Key points
From the paper's conclusion- We develop a closed-loop software-in-the-loop testbed in which a setpoint model trained on real occupancy data drives a physics-based thermal zone through a declarative governance plane, with outcomes scored by an independent safety oracle, and we run the same governance logic on a real MQTT stack with an in-process policy decision point and a hash-chained audit log.
Abstract
Which runtime governance mechanisms reduce physical risk when a learned controller drives a building's climate, and under what conditions? We develop a closed-loop software-in-the-loop testbed in which a setpoint model trained on real occupancy data drives a physics-based thermal zone through a declarative governance plane, with outcomes scored by an independent safety oracle, and we run the same governance logic on a real MQTT stack with an in-process policy decision point and a hash-chained audit log. Under distribution shift, admission control reduces unsafe physical exposure by 19.4%, from 1185.3 to 954.8 °C·min, whereas adding checkpoint rollback reduces it by only a further 0.2% in the reference run (0.1-0.4% across sensor noise seeds): the governance decision takes 0.44 ms while physical recovery takes a median of 61 min. Prevention therefore outperforms recovery in the studied thermal system, and the remaining avoidable exposure is driven by the policy's estimate of occupancy context. A deterministic single-rule thermostat incurs 50% more exposure under shift while the learned controller uses a 38% higher heating demand proxy: a safety-demand trade-off, not evidence that learned control is necessary. A plant sweep yields an operating envelope criterion for inertial plants: rollback contributes materially to safety only when the plant is restored before the next command arrives and sampled before it can leave the safe set; on slower plants it removes at most 14.7%, with a transition band in between. No physical hardware was operated.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- From Data to Valves: A Self-Learning, Production-Grade Edge Stack for Sustainable HVAC ControlarXiv · 2026
- Safe Reinforcement Learning for Buildings: Minimizing Energy Use While Maximizing Occupant ComfortEnergies · 2025
- Improving Building Energy Efficiency with an Indoor Environmental World Model and Counterfactual Adaptive LearningarXiv · 2026
- Very Exciting: Zero-Shot Model Predictive Control of Buildings via Excitation-Based Generalized Transfer Learning ModelsarXiv · 2026
- A reproducible method to generate multi-building, multi-climate HVAC operation datasets with a stochastic exploratory controllerMethodsX · 2026
- Online Identification Can Replace a Floor-Plan Prior on Unseen BuildingsarXiv · 2026