Gas-Generation Characteristics of Mineral Oil, Natural Ester and Synthetic Ester Under Multiple Partial-Discharge Regimes: Implications for Dissolved Gas Analysis
Xuelei Wang, Wenbing Zhu, Jinxuan Song, Jinyang He, Zhicheng Wu
Key points
From the paper's conclusion- The gas-generation characteristics of mineral oil (Kunlun KI50X), natural ester (FR3) and synthetic ester (MIDEL 7131) were investigated under four representative PD regimes: corona, surface, cavity and floating-electrode discharge, with insulating pressboard present; the corona configuration was tested additionally without pressboard, and all configurations were further examined under higher-ener
Abstract
Partial discharge (PD) is a major cause of insulation degradation in oil-immersed power equipment, and dissolved-gas analysis (DGA) is the principal chemical diagnostic tool for such faults; conventional DGA criteria, however, were developed for mineral oil and may not transfer directly to ester-based insulating liquids. The gas-generation characteristics of mineral oil (Kunlun KI50X), natural ester (FR3) and synthetic ester (MIDEL 7131) were investigated under four representative PD regimes: corona, surface, cavity and floating-electrode discharge, with insulating pressboard present; the corona configuration was tested additionally without pressboard, and all configurations were further examined under higher-energy spark discharge, on a closed-loop oil-circulation platform combining synchronized phase-resolved PD (PRPD) monitoring with automatic oil chromatography. Under moderate-energy PD, mineral oil produces mainly H2 together with the hydrocarbon gases CH4 and C2H2, whereas both esters preferentially liberate H2 and CO, reflecting their ester linkages; the presence of pressboard further elevates CO/CO2 through cellulose decomposition. Under intermittent sparking, the C2H2 and H2 production rates converge across the three fluids, indicating that molecular-structure effects diminish once repeated dielectric breakdown occurs. Within each PD mode, estimated cumulative discharge energy and cumulative dissolved-gas volume are linearly related, but this linearity deteriorates when data from different modes are pooled. Conventional mineral oil DGA schemes therefore cannot be applied uncritically to ester-filled apparatus; reliable fault diagnosis requires combined electrical (PRPD-based energy quantification) and oil-specific chemical (DGA) diagnostics.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Partial Discharge Characteristics and Aging Identification Model of Polymer Insulation Materials in Environmentally Friendly Insulating Liquids Under Electro-Thermal Aging ConditionsPolymers · 2026
- Study on pyrolysis gas generation characteristics of insulating oil under electro-thermal action based on ReaxFF simulation.Frontiers in chemistry · 2026
- Investigating High Intensity Thermal Faults in Ester-Based Transformer Oil: A Dissolved Gas Analysis ApproachEngineering Technology & Applied Science Research · 2026
- Over 40 Years of Ester Dielectric Liquids for High-Voltage Transformers: A Retrospective on Evolution, Performance, and Future Prospects (An Extended report of the Hans Tropper Memorial Lecture 2025)IEEE Electrical Insulation Magazine · 2026
- Research progress of online monitoring techniques for dissolved gas analysis in insulating oilFrontiers in Chemistry · 2025
- Fault Diagnosis of Natural Ester Oil Filled Transformers Using Mechanism Inspired Structured Tokens and Auxiliary Supervision with Full Window TrendsInventions · 2026