Experimental Study on the Suppression of Lithium Iron Phosphate Battery Fires Using Thermoresponsive Hydrogel
Qingyu Chen, Yang Liu, Shunbing Zhu, Menglan Zhang, Yu Lu
Key points
From the paper's conclusion- We screened a hydrogel containing methylcellulose (MC), sodium alginate (SA), magnesium chloride (MgCl2), ammonium polyphosphate (APP), and glycerol by measuring its viscosity, thermal gelation, flame suppression performance, and mass loss during heating.
Abstract
This study links the formulation of a thermoresponsive hydrogel to the effect of dilution on three stages of lithium iron phosphate (LFP) battery fire suppression: flame extinction, cooling during spraying, and temperature rebound after spraying. We screened a hydrogel containing methylcellulose (MC), sodium alginate (SA), magnesium chloride (MgCl2), ammonium polyphosphate (APP), and glycerol by measuring its viscosity, thermal gelation, flame suppression performance, and mass loss during heating. We then compared five dilutions of the selected stock formulation with pure water in fire tests on 20 Ah LFP cells. The selected stock formulation comprised 0.8% MC, 0.8% SA, 0.7% MgCl2, 3% APP, and 4% glycerol. The 7% dilution extinguished visible flames in 11 s, compared with 23 s for pure water. Over the 75 s discharge period, the five-point mean temperature fell by 269.0 °C with the 7% dilution, a 74.45% greater reduction than with pure water. The spatial maximum fell by 598 °C over the same interval, giving an average cooling rate of 7.973 °C·s−1. The 9% dilution produced a larger drop in mean temperature (279.6 °C), whereas the 7% dilution showed lower temperature rebound rates after spraying ceased. The post-extinguishment rebound rates of the average and maximum temperatures were 0.0041 and 0.0448 °C·s−1, respectively. The specific enthalpy reached 2532.34 J·g−1, with an endothermic interval of 23.4~178.3 °C. Thermally induced gelation, evaporative heat absorption, stable surface coverage, prolonged action through water retention, and gas- and condensed-phase flame retardancy jointly enabled rapid extinguishment, sustained cooling, and reduced short-term temperature rise and reignition risks. These findings provide a basis for developing aqueous extinguishing materials for LFP battery fires.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- In Situ Generation of Gel Foam via Heat-Accelerated Calcium Ion Release From Nano-CaCO3 for Lithium-Ion Battery Fire Suppression and Prevention.Advanced science (Weinheim, Baden-Wurttemberg, Germany) · 2026
- Eco-friendly cellulose-derived thermoresponsive hydrogels for next-generation forest fire prevention and controlMaterials Today Chemistry · 2026
- Experimental Study on Suppression of Lithium-Ion Battery Fires Using Clean and Efficient Aqueous Fire Extinguishing AgentsSAE technical papers on CD-ROM/SAE technical paper series · 2026
- Ultrathin Hydrated Salt Gel with High Thermal Storage Density and Switchable Low Thermal Conductivity to Suppress Battery Thermal Runaway PropagationGreen Energy and Intelligent Transportation · 2026
- Comprehensive Experimental Study on the Fire Hazards of LiPF6-Based ElectrolytesFire · 2026
- Inhibition Mechanisms of Lithium-Ion Battery Deflagration by the Free Space and Aerogel Wall Surface Inside an Explosion-Proof Power EnclosureEnergy & Fuels · 2026