Smoke Detector Arrangement in Suspended (Double) Ceilings: A Numerical Investigation Based on International Fire Protection Standards
Jovan Ničković, Radoje Jevtić, Momčilo Ranđelović, Stefan M. Popović
Key points
From the paper's conclusion- The results showed that fire growth rate was the dominant factor affecting detector activation time, while suspended-ceiling height, ceiling area, and burner location substantially influenced smoke transport and detector response.
Abstract
The performance of automatic smoke detection systems depends strongly on the appropriate placement of smoke detectors, particularly in compartments with suspended (double) ceilings, where smoke movement is affected by ceiling geometry. This study presents a numerical investigation of smoke detector arrangements based on the requirements of five international fire protection standards using the Fire Dynamics Simulator (FDS). The 180 simulations examined four fire growth rates (slow, medium, fast, and ultra-fast), five suspended-ceiling heights, three suspended-ceiling areas, and three burner locations. The results showed that fire growth rate was the dominant factor affecting detector activation time, while suspended-ceiling height, ceiling area, and burner location substantially influenced smoke transport and detector response. Increasing the distance between the suspended and main ceilings generally reduced activation times, whereas reducing suspended-ceiling area from 0.9P to 0.5P shortened mean activation time by 15.12%. With 83.3% overall detector-level activation coverage, the results demonstrate substantial differences in detector response between detectors installed at the suspended-ceiling and main-ceiling levels and provide engineering insight into smoke detector arrangements in spaces with suspended ceilings.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Fire Smoke Transport in Inclined Evacuation Passages of Deep-Buried Metro Stations: A Reduced-Scale Experimental StudyFire · 2026
- Convective-Buoyancy Scaling and Thermal Attenuation of Two-Stage Smoke Propagation in an Open-Door Metro Carriage–Tunnel FireFire · 2026
- Research on the Evolution Characteristics and Collaborative Detection Strategies for Bottom Oil-Spill Fires in Oil-Immersed TransformersFire · 2026
- Long-range vision-based displacement sensing for structural health monitoring of fire-exposed spatial structuresSmart Materials and Structures · 2026
- Computational investigation of smoke management performance in a large enclosed sports using fire dynamics simulator: a comparative assessment of natural and mechanical ventilation strategiesJournal of Thermal Analysis and Calorimetry · 2026
- A Leakage-Aware Evaluation Framework and Benchmark for Edge-Based Multi-Sensor Fire and Smoke DetectionInformation · 2026