Energies

Experimental Hardware-in-the-Loop Assessment of Automatic Voltage Regulator Mismatch Effects in Parallel-Operating Shipboard Generators

Tymoteusz Zaleski, Dariusz Tarnapowicz, Zbigniew Matuszak, Marek Jaśkiewicz, Radoslaw Ptak

Key points

From the paper's conclusion
  • The platform enables safe and repeatable assessment of physical AVRs during parallel generator operation without the use of high-power synchronous generators.

Abstract

Parallel operation of synchronous generators in a shipboard power system requires properly coordinated Automatic Voltage Regulators (AVRs). AVR mismatch can cause unequal reactive power sharing and increased generator currents. In operational and service practice, the possibilities for safe and repeatable diagnosis of AVR settings under parallel-operation conditions are limited. Conventional workshop tests do not reproduce the complete coupling between the regulators, common-bus voltage, stator currents, and reactive power flow. This paper presents the development and experimental assessment of a Hardware-in-the-Loop platform for testing two physical digital AVRs coupled to real-time models of two synchronous generators, prime movers, a common main switchboard (MSB), and a load. The platform uses a common voltage interface and inverter-based stator-current reproduction interfaces. The current-reproduction interface was functionally validated. A reference operating test and tests of the effects of differences in proportional gain, integral time, voltage reference, and voltage droop settings were performed. Matched AVR settings provided stable operation following load changes. Mismatched voltage references and voltage droop settings caused persistent unequal reactive power sharing. Zero voltage droop caused oscillatory reactive power exchange and increased generator currents. The platform enables safe and repeatable assessment of physical AVRs during parallel generator operation without the use of high-power synchronous generators.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Experimental Hardware-in-the-Loop Assessment of Automatic Voltage Regulator Mismatch Effects in Parallel-Operating Shipboard Generators — Science Skim