Substation Operational State Assessment and Short-Term Prediction Based on Micro-Phasor Measurement Unit Data

Peng Li, Kyung-Min Lee, Yong-Sung Choi

Key points

From the paper's conclusion
  • This study developed a field-measurement framework for substation operating-state assessment and next-day prediction using 32 micro-phasor measurement units (μPMUs) at Yeonggwang Substation, Republic of Korea.

Abstract

This study developed a field-measurement framework for substation operating-state assessment and next-day prediction using 32 micro-phasor measurement units (μPMUs) at Yeonggwang Substation, Republic of Korea. Positive-sequence voltage deviation, voltage unbalance factor, frequency deviation, and normalized one-minute positive-sequence voltage range were used to calculate the Health Index (HI) and Running State Index (RSI). The daily RSI combined the full-day mean with the mean of the lowest 5% of valid minute scores. The 21-day record yielded 480 development and 160 held-out μPMU-day pairs. Four-fold expanding-window validation selected Ridge regression with F4 inputs (α = 100; MAE = 0.4672). On the independent test set, Historical Mean achieved lower μPMU-level and station-level MAEs (0.2993 and 0.1809 RSI points) than Ridge (0.3918 and 0.2105). In nine development-period sensitivity scenarios, changes in feature weights, scoring anchors, the voltage-range definition, and daily aggregation affected the resulting RSI; HI equaled 100 in 96.25% of valid minutes. All four models predicted scores above the cutoff for each of the 11 test cases with RSI at or below P10. The findings demonstrate an auditable measurement-to-assessment pipeline and the importance of simple baselines, while the short test period, upper-score saturation, and low-score misses limit operational deployment claims.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers