Internal Model Control-Based Time-Delay Compensation for Small-Signal Stability Improvement in Inverter-Fed Islanded Microgrids
Naresh Kumar Vemula, Muhammad Asif Hasan, Mohammad Irshad, Pratikanta Mishra, Alok Kumar Verma
Key points
From the paper's conclusion- The effectiveness of the proposed approach is verified through comparison with a conventional IMC controller without delay compensation using the OPAL-RT OP4510 real-time simulator, where it reduces the frequency overshoot after load changes from about 30% to below 4% of the steady-state deviation.
Abstract
Inverter technology has emerged as a key enabler for renewable energy integration and power delivery in modern microgrids (MGs). Digital time delays associated with measurement, computation, and pulse-width modulation can significantly affect the dynamic performance and stability of islanded inverter-fed microgrids. This paper presents an internal model control (IMC)-based current controller with explicit digital time-delay compensation to improve stability and dynamic performance by addressing delay-induced oscillatory interactions among different control layers. A comprehensive small-signal model is developed by incorporating power, voltage, and current control loops, digital time delay, LC filter, network, and load dynamics. The third-order Padé model of the delay is verified against the exact delay, and system stability is evaluated through eigenvalues, damping ratios and participation factors. At the nominal delay of 15 μs (1.5Ts, Ts=10μs), the current-loop modes of the IMC without compensation are almost undamped (ζ≈0.002) and become unstable beyond 15.25 μs, whereas the proposed controller damps the same modes with ζ=0.29 and remains stable up to 24.75 μs. The proposed design is also compared with a Smith predictor, its robustness to filter, line and load variations is assessed, and particle swarm optimization (PSO) with an explicit stability constraint raises the minimum damping ratio to 0.62. The effectiveness of the proposed approach is verified through comparison with a conventional IMC controller without delay compensation using the OPAL-RT OP4510 real-time simulator, where it reduces the frequency overshoot after load changes from about 30% to below 4% of the steady-state deviation.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Distributed Prescribed-Time Secondary Control for Islanded AC Microgrids Under Communication DelaysIEEE Internet of Things Journal · 2026
- Equivalent virtual inertia modeling and time-constant analysis for multi-generator DC microgridsJournal of Renewable and Sustainable Energy · 2026
- A Hybrid LQR–PI Control Strategy with Virtual Impedance for Next-Generation Inverter-Based Microgrids: Enhanced Dynamic Stability and Power QualityEnergies · 2026
- Event-triggered adaptive fixed-time sliding mode control for voltage regulation of spacecraft DC microgridsEngineering Research Express · 2026
- Fully Distributed Event-Triggered Secondary Control for Islanded Microgrid Restoration With Communication Link FaultsIEEE Transactions on Automation Science and Engineering · 2026
- Active damping and harmonic suppression strategy of LCL Grid-tied inverters based on single inverter-side inductor current feedback considering sampling delayJournal of Physics: Conference Series · 2026