Energies

Setting the Sensible and Latent Performance of Air-to-Air Plate Heat Exchangers at the Manufacturing Stage by Multi-Nozzle 3D Printing

Pawel Znaczko, Kazimierz Kaminski, Norbert Chamier-Gliszczynski

Key points

From the paper's conclusion
  • The nozzle temperature is thus a manufacturing parameter that adjusts the latent performance of a printed core without changing its geometry.

Abstract

Heat recovery ventilation requires exchangers whose sensible and latent performance can be matched to the climate, yet in membrane cores the latent performance is fixed before assembly and the plate geometry is limited by the membrane. This study presents a new manufacturing method in which a ten-nozzle multi-extruder prints a counterflow plate core by Fused Deposition Modeling in one process and, unlike in existing cores, the wall material and the nozzle temperature set the latent transfer independently of the channel geometry. Five cores of identical geometry were tested at 150 m3/h in a modified air handling unit at outdoor temperatures of 7.2–8.9 °C: a PETG core as a sensible-only reference and four foaming PLA cores printed at nozzle temperatures of 200–230 °C. The supply-side temperature ratio ηθ,su remained between 81.4% and 84.0%, whereas the moisture ratio ηx,su rose from 0.0% for PETG to 28.0% at 220 °C and fell to 18.0% at 230 °C, where the cellular wall structure collapsed. The nozzle temperature is thus a manufacturing parameter that adjusts the latent performance of a printed core without changing its geometry.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers