Architecture-Driven Observer–Energy Event Discrimination in Grid-Connected Virtual Synchronous Generators
Sadi Serdar Güneli, Muhammet Ali Arserim
Key points
From the paper's conclusion- For a 30 kW local load, simulated disconnection is detected 0.553 s after the grid opens (threshold crossing plus dwell), and the fault and grid-connected load step raise no false alarm; no speed advantage is claimed.
Abstract
Grid disconnection in converter-dominated systems is difficult to distinguish from faults and load changes with comparable or larger transients. This paper investigates an observer–energy event-discrimination framework built on a role-separated architecture for a grid-connected virtual synchronous generator (VSG): the VSG keeps the voltage-forming role, so its power balance is available internally, while a phase-locked loop (PLL) acts only as an external, communication-free observer at the point of common coupling. Three signatures are examined: PLL-frequency deviation, VSG–PLL phase deviation, and the power-balance signature. Phase deviation settles at a nonzero value after a permanent grid-connected load step, and is excluded from the decision rule. In steady state, the swing equation and damping approximately relate the two thresholds (0.10 p.u. ≈ 0.1006 Hz); both must be exceeded for 300 ms. For a 30 kW local load, simulated disconnection is detected 0.553 s after the grid opens (threshold crossing plus dwell), and the fault and grid-connected load step raise no false alarm; no speed advantage is claimed. The deficit-side non-detection-zone edge lies near 26.6 kW under reference conditions and varies with reactive-power mismatch, load model, and power reference. Offline one-at-a-time variations of parameters, grid strength, X/R, and voltage noise preserved 30 kW detection without false alarms.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- A Transient Stability Enhancement Control Strategy for Virtual Synchronous GeneratorsIEEJ Transactions on Electrical and Electronic Engineering · 2026
- Enhancing Transient Stability of VSG-Controlled Converters Under Grid Frequency DisturbancesarXiv · 2026
- Coordinated VSG Control for Grid-Connected, Islanded, and Grid-Reconnection Operations in Rural Low-Voltage Distribution Networks Considering Feeder Length and Load DisturbancesEnergies · 2026
- Enhanced Grid-Forming Operation of Virtual Synchronous Generator UnitsIEEE Transactions on Power Delivery · 2025
- Analysis of voltage-power security and stability boundaries for virtual synchronous control based on a transient energy functionFrontiers in Energy Research · 2026
- Mechanism-Based Online Security Boundaries of Grid-Following Converters in Weak Grids with a Verified One-Sided Risk LimitElectronics · 2026