Energies

Architecture-Driven Observer–Energy Event Discrimination in Grid-Connected Virtual Synchronous Generators

Sadi Serdar Güneli, Muhammet Ali Arserim

Key points

From the paper's conclusion
  • For a 30 kW local load, simulated disconnection is detected 0.553 s after the grid opens (threshold crossing plus dwell), and the fault and grid-connected load step raise no false alarm; no speed advantage is claimed.

Abstract

Grid disconnection in converter-dominated systems is difficult to distinguish from faults and load changes with comparable or larger transients. This paper investigates an observer–energy event-discrimination framework built on a role-separated architecture for a grid-connected virtual synchronous generator (VSG): the VSG keeps the voltage-forming role, so its power balance is available internally, while a phase-locked loop (PLL) acts only as an external, communication-free observer at the point of common coupling. Three signatures are examined: PLL-frequency deviation, VSG–PLL phase deviation, and the power-balance signature. Phase deviation settles at a nonzero value after a permanent grid-connected load step, and is excluded from the decision rule. In steady state, the swing equation and damping approximately relate the two thresholds (0.10 p.u. ≈ 0.1006 Hz); both must be exceeded for 300 ms. For a 30 kW local load, simulated disconnection is detected 0.553 s after the grid opens (threshold crossing plus dwell), and the fault and grid-connected load step raise no false alarm; no speed advantage is claimed. The deficit-side non-detection-zone edge lies near 26.6 kW under reference conditions and varies with reactive-power mismatch, load model, and power reference. Offline one-at-a-time variations of parameters, grid strength, X/R, and voltage noise preserved 30 kW detection without false alarms.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers